Rszgf High Voltage Test Equipment 1500 Meter Below Altitude For Hipot
RSZGF series DC high voltage generator is according to the Chinese industry standard ZBF 24003-90 "portable dc high voltage generator general technical conditions" requirement, research and manufacture of portable dc high voltage generator, applicable to the electric power department, power department of factories and mines, scientific research units, railway, chemical industry, power plant, etc for zinc oxide lightning arrester, magnetic blow arrester, power cable, generator, transformer, switch equipment of dc high voltage test.
Technical parameter |
40 | 60 | 60 | 120 | 120 | 120 | 200 | 200 | 200 | 300 | 400 |
/4 | /2 | /5 | /2 | /3 | /5 | /2 | /3 | /5 | /2 | /5 | |
Rated voltage(kV) |
40 | 60 | 60 | 120 | 120 | 120 | 200 | 200 | 200 | 300 | 400 |
Rated current(mA) |
4 | 2 | 5 | 2 | 3 | 5 | 2 | 3 | 5 | 2 | 5 |
Rated power(W) |
160 | 120 | 300 | 240 | 360 | 600 | 400 | 600 | 1000 | 600 | 2000 |
Voltage measurement accuracy |
Data display instrument±(1.0 % reader±0.2kV) | ||||||||||
Current measurement accuracy |
Data display instrument±(1.0 % reader±0.2) | ||||||||||
Ripple ratio |
≤0.5% | ||||||||||
Voltage stability |
Random fluctuation, line-voltage variation±10% ≤1% |
||||||||||
Overload capacity |
When No-load voltage higher than rated voltage 10%, use 10 min. The max. charging current is 1.5 time rated current |
||||||||||
Power |
Single AC 50Hz,220V±10% |
||||||||||
Work type |
Interruption use | ||||||||||
Max continuous time is 30 min. | |||||||||||
Work environment |
Temperature:-10~40℃ | ||||||||||
Relative humidity: Indoor temperature is 25℃, ≦85% |
|||||||||||
Altitude: 1500 meter below |
|||||||||||
With capacitive load capacity |
The sample (s) be unlimited capacitance |
||||||||||
Use 1.5 time rated current charging |
|||||||||||
Structural features |
Epoxy glass fiber reinforced plastic electrical insulation voltage double cone |
||||||||||
Air insulated No leakage |
|||||||||||
The characteristics of box |
High precision 0.75UDC--1mA One touch button(Accuracy≤1.0%) suitable for zinc oxide lightning arrester test |
||||||||||
Overvoltage protection using dial the code set, be clear at a glance |
|||||||||||
Lie the dual-purpose international standard case, live more convenient |