RSCJ-V AC HV Impulse High Voltage Impulse Voltage Test System for Lightning Test
Impulse voltage generator is mainly used for full wave of lightning impulse voltage, lightning impulse voltage clipping wave and operation impulse voltage wave test of electric power equipment, etc., to test insulation performance. Impulse voltage generator a power supply device that mimics the impulse voltage of lightning and operating overvoltage. It is mainly used in insulation shock withstand voltage and dielectric shock breakdown, discharge and other tests.
The device can provide a complete set of impulse voltage (current) generators of various waveform series. The impact test device is mainly composed of generator body, cut-off wave, voltage divider, four-component console (the console is divided into microcomputer type and common type), digital waveform recording system, etc.
Product Features
1. Small loop inductance and band-stop filtering measures can produce standard shock wave under large capacitance load with large load capacity.
2. High voltage utilization coefficient, no less than 85% and 80% of thunder wave and operation wave respectively.
3, Wave modulation convenient, simple operation, good synchronization performance, reliable action.
4, The use of constant current charging automatic control technology, high degree of automation, strong anti-interference ability.
Standard Voltage(kv) | Impact capacity(μF) | Levels of capacitance(μF) | Impact energy(kJ) | Level of voltage(kv) | Level | Weight(kg) |
±300 - ±900 | 0.133-0.111 | 0.4-1 | 6-45 | ±100 | 3-9 | 547-1378 |
±1000 - ±1600 | 0.05-0.0937 | 0.5-1.5 | 25-120 | ±100 | 10-16 | 1366-1880 |
±1800 - ±2400 | 0.05-0.0833 | 0.5-1.5 | 90-240 | ±200 | 9-12 | 7353-11574 |
±2800 - ±3200 | 0.0357-0.0625 | 0.5-1.5 | 140-320 | ±200 | 14-16 | 10266-15680 |
±3600 - ±4800 | 0.0278-0.03125 | 0.5-2 | 80-240 | ±200 | 18-24 | 15480-23500 |