100A Transformer Winding Ohmmeter
Model: TWO-1100S
Maximum 100A current for measuring winding resistance of power transformer
Transformer Winding Ohmmeter is designed to measure the dc resistance of all types of magnetic windings accurately. It can test transformers and rotating machine windings and perform low-current resistance measurement on connections, contacts and control circuits. The maximum test current of TWO-1100S can be up to 100A.
Main Features
1) Adopt 4-wire method for resistance measurement
2) DC test current up to 100 A maximum
3) User-selectable maximum current range
4) Resistance measurement from 50μΩ to 4Ω
5) Fast auto safety discharge circuit
6) Able to download test results via USB interface
7) Able to print the test results directly via built-in printer
Technical Data
◇DC output range: 100A, 50A, 20A, 10A, 5A
◇Resistance measurement
30μΩ-100mΩ @ 100A
100μΩ-200mΩ @ 50A
200μΩ-1Ω @ 20A
500μΩ-2Ω @ 10A
2mΩ-4Ω @ 5A
◇Measuring accuracy: ±0.2% reading ± 2μΩ
◇Resolution: 0.1μΩ
◇320×240 colour LCD screen for display
◇USB port for downloading results
◇Built-in printer for printing test results directly
◇Max. memory capacity: 1000 test results
◇Power supply: customized(AC220V/120V±10%, 50Hz/60Hz optional)
◇Dimension: 400x225x350mm(15.75x8.86x13.78 in)
◇Weight: 19.5kg(42.99 lb)
◇Environmental Conditions
storage temperature: -20℃~60℃
humidity: <90%
operating temperature: -10℃~50℃
◇Safety Qualifications and EMC
Safety: designed in accordance with IEC61010-1
EMC: light industrial IEC 61326
Transformer Winding Ohmmeter TWO-1100S is used for measuring winding resistance of power transformer, which the maximum test current can be up to 100A.