CYYZ41Y Pressure Transmitter Range -100kPa~0~4MPa Output 4~20mA,0~5VDC,1~5VDC Power Supply 9~32VDC Accuracy 0.5%FS
Suitable for the refrigeration and air conditioning industry, the pressure transmitter type CYYZ41Y is fully metal-sealed by laser process, compatible with all common refrigerants, and its robust construction protects against mechanical effects such as shock and vibration. It also has diversified advantages such as range and electrical connection, which is convenient to match different working conditions.
Base parameters | |
Measuring medium | Liquid or gas (compatible with contact material) |
Pressure range | -100kPa~0~4MPa (see range selection table for details) |
Pressure mode | Positive and negative pressure, sealing pressure (zero absolute pressure 101.3kPa) |
Output signal | 4~20mA,0~5VDC,1~5VDC |
Supply voltage | 9~32VDC |
Media temperature | -40~85℃ |
On-time | 20ms |
Accuracy class | 0.5%FS(Reference conditions temperature 15~25°C, humidity 45~75%RH) |
Stable performance | ±0.2% FS/year |
Temperature drift | ±0.02%FS/℃(≥-10℃) ±0.05%FS/℃(<-10℃) |
Degree of protection | IP65 Note: The above protection level refers to the electrical connection achieved after it is complete |
Durable performance | 10X10⁶ times (lower range to upper range cycles) |
Response frequency | 100Hz |
Overall weight | ≈113g |
Resolution | 0.01%FS |
Maximum power | |
Output signal | 4~20mA,0~5VDC,1~5VDC, |
Power supply range | |
Load characteristics | |
Voltage type | ≥10kΩ |
Current type | Current load ≤{(Us-7.5)÷0.02}Ω(Us=Supply voltage2) |
Environmental conditions | |
Ambient temperature | -40~85℃ |
Ambient humidity | 0%~95%RH(no condensation, no condensation) |
Overall material | |
diaphragm | 316L stainless steel (contact with the medium to be measured) |
Process connection | 316L stainless steel (contact with the medium to be measured) |
enclosure | 316L stainless steel |
Press the nut | ABS engineering plastics |
Hirschmann joints | ABS engineering plastics |
Mechanical stability | |
Seismic performance | 10g(20… 2000Hz) in accordance with IEC60068-2-6 standard |
Impact resistance: | 500g/ms conforms to IEC60068-2-27 standard |
Electrical protection | |
Short-circuit protection | perpetual |
Anti-polarity protection | No damage, but not working |
Insulation resistance | ≥100MΩ500VDC |
Dielectric strength: | 500VAC |
Output limits | |
The output is minimal | 3.8mA,0,0.001VDC,0.001VDC |
Output maximum | 26mA,12VDC,5VDC |