CWS19Y Wall-Mounted Humidity And Temperature Transmitter Planting And Breeding Hospital Ward, Clean Rooms HVAC
CWS19Y wall-mounted temperature and humidity transmitter is carefully designed, excellent quality, suitable for indoor temperature and humidity monitoring in various occasions, temperature range can be adjusted, with display and without display two options, and cost-effective.
Base parameters | |
Measuring medium | Gas (compatible with contact material) |
Temperature range | -40~0~125℃ |
Humidity range | 0-100%RH (relative humidity) |
Overall weight | With display ≈ 160g, no display ≈ 138g |
Response frequency | ≤2Hz |
Stable performance | ±1% RHFS/year, ±0.2°C/year |
Degree of protection | IP65 |
Speed of response | Temperature response time, no filter 15s, with filter 55s; Humidity response time, 15s without filter, 35s with filter (temperature at 10°C per step, humidity at 10%RH per step, gas flow rate of 0.1m/s) |
Output power | |
Output signal | 4~20mA,RS485,0~10VDC |
Power supply range | 12~24VDC,24VDC |
Maximum power | |
4~20mA | No display≤0.05Us(W), 0.06Us(W) with display≤ |
RS485 | No display≤0.015Us(W), 0.025Us(W) with display≤ |
0~10VDC | No display≤0.015Us(W), 0.025Us(W) with display≤ |
Load characteristics | |
Voltage type | ≥100kΩ |
Current type | ≤200Ω |
Environmental conditions | |
Ambient temperature: | -40~85℃ |
Ambient humidity: | 0%~95%RH( Non-condensing, non-condensing) |
Electrical protection | |
Short-circuit protection | perpetual |
Anti-polarity protection | No damage, but not working |
Insulation resistance | ≥100MΩ,500VDC |
Dielectric strength | 500VAC |
Output limits | |
4~20mA | Output min. 4mA and output max 20mA |
RS485 | Output minimum 0, output maximum 1650/1000 |
0~10VDC | Output minimum 0.001VDC, output maximum 10VDC |
Overall material | |
Body housing | ABS engineering plastics (contact with the measured medium) |
filter | Polyethylene (density 50 μm) (contact with the measured medium) |
Cable locking head | Nylon (lock wire diameter 4~6mm) (contact with the measured medium) |
display | LCD display with backlight |
Seals | Nitrile rubber (contact with the medium to be measured) |
Mechanical stability | |
Seismic performance | 5g(20… 2000Hz) in accordance with IEC60068-2-6 standard |
Impact resistance | 500g/1ms conforms to IEC60068-2-27 standard |