Scope of application:
The second-level lightning protection box is mainly installed in the floor power distribution, computer room power distribution and other environments, as the second-level lightning protection of the power distribution system, discharges the remaining surge, and cooperates with the first-level lightning protection box to meet the lightning protection acceptance Requirements and protection needs.
The main parameters:
Maximum continuous working voltage Uc: 385VAC
Nominal discharge current In(8/20μs): 20kA or 40kA
Maximum discharge current Imax (8/20μs): 40kA or 80kA
Protection level Up: 1.8kV or 2.1kV
Protection mode: three-phase 4P, single-phase 2P
Product size: 350*260*130mm
Product Description:
Adopting Class II SPD to combine “3+1” circuit, protecting low voltage equipment from surge damages, applied in TT system, designed according to IEC61643-1/GB 18802.1
Main character:
1. Green light indicates normal and red light indicates fault for operation
2. Built-in circuit breaker, and thermal disconnection device, when the fault occurred, the thermal disconnection device will cut off the SPD from the power net, the green window will change
3. Impulse counter function, recording the lightning events
4. External wiring terminal, easy for connection, suitable for indoor application
Type | BT 5L CM 275/40 4P | BT 5L CM 385/40 4P | BT 5L CM 275/40 3+1 | BT 5L CM 385/40 3+1 | |
Order No. | 840 883 | 840 887 | 840 884 | 840 888 | |
Norminal a.c. voltage | UN | 230V/400V | 230V/400V | 230V/400V | 230V/400V |
Rated voltage (max. continuous a.c voltage) L/N | Uc | 275V | 385V | 275V | 385V |
Rated voltage (max. continuous a.c voltage) N/PE | Uc | 275V | 385V | 255V | 255V |
Nominal discharge current (8/20µs) L/N | In | 20KA | 20KA | 20KA | 20KA |
Nominal discharge current (8/20µs) N/PE | In | 20KA | 20KA | 40KA | 40KA |
Max. discharge current (8/20µs) L/N | Imax | 40KA | 40KA | 40KA | 40KA |
Max. discharge current (8/20µs) N/PE | Imax | 40KA | 40KA | 65KA | 65KA |
Voltage protection level L/N | Up | ≤1.25KV | ≤1.8KV | ≤1.25KV | ≤1.8KV |
Voltage protection level N/PE | Up | ≤1.25KV | ≤1.8KV | ≤1.5KV | ≤1.5KV |
Follow current extinguishing capability at Uc (N/E) | IL | 100Arms | 100Arms | ||
Operating temperature range | -40℃…+80℃ | ||||
Cross-sectional area | 25mm2 solid/35mm2 flexible | ||||
Enclosure material | black metal housing (die-casting Aluminum) | ||||
Test standards | YD/T 1235.1; GB 18802.1; IEC 61643-1 | ||||
Certification | CE (LVD, EMC) |