Technical Data:
Model*1 | HP1106B | HP1106H | HP1110B | HP1110H |
rated power | 6KVA/5.4KW | 10KVA/9KW | ||
Input and output modes | Single phase in single phase out | |||
Electrical Characteristics | ||||
Product topology | On-line double conversion | |||
Input voltage | 220/230/240V | |||
Input voltage range | 120-275V,176-270V Full power operation | |||
Output Voltage / Output Distortion | 220V/230V/240V ±1 %, THDU<3% | |||
Enter the frequency range | 45Hz-64Hz, 50/60Hz Adaptive | |||
effectiveness | Up to 90%(Online) | |||
Short circuit current | 82A | 137A | ||
Overload capacity | 105%-125% : 1min, 125%-150% : 30sec. | |||
And machine | Maximum in parallel machine 3 sets(Optional) | |||
Power factor | 0.9 | |||
Conversion time | Zero millisecond conversion | |||
Battery voltage*2 | 192VDC(Optional 204VDC/216VDC/228VDC/240VDC) | |||
Charging current *3 | 4A | 8A | 4A | 8A |
Battery type | Valve regulated lead-acid battery | |||
Standby time/min | 〉6/18 | / | 〉4/11 | / |
(Full load / half load) | ||||
Communication | ||||
Communication port*4 | RS232 | |||
Scalable slots | 1 pcs (Suitable for SNMP cards, ModBus-RTU cards, dry contact cards) | |||
Operating environment, technical specifications and standards | ||||
Operating environment temperature and humidity | 0 to 40°C / 20%~90% | |||
Noise | <55dB | |||
Safety | IEC/EN 62040-1 | |||
EMC | IEC/EN 62040-2 | |||
Certification | TLC / radio certification / energy-saving certification | |||
Physical parameters | ||||
W | 250 | 245 | 250 | 245 |
L | 515 | 530 | 515 | 530 |
H | 608 | 455 | 608 | 455 |
Weight(kg) | 57 | 17.5 | 65 | 20 |