Modbus RTU Active Power Filter Parallel 50-300A Full Response Time ≤ 20ms
Functions Indexes:
Why Choose Us?
Technical Details:
Output current capacity(A) | 45 | 75 | 100 | 150 | 200 | |
AC Input | Rated voltage | 380×(1±15%)V | ||||
Rated Frequency | 50×(1±1%)Hz | |||||
Rated topology | Three-phase three-wire | |||||
Technical
| Orders of harmonic compensating | Within 5~13: selectable Or within 5~25: all compensation | ||||
Compensating rate (THDILoad-THDIS)/ THDILoad | ≥85% | |||||
Reactive power compensating | Determined by priority
| |||||
Full response time | ≤20ms | |||||
Overload Protection | Automatically limited to the rated output current | |||||
Active power loss | <5%Rated capacity | |||||
Noise | <65dB | |||||
Environment & | Operating temperature | -10℃~+45℃ | ||||
Storing Temperature | -20℃~+65℃ | |||||
Relative humidity | <90%(25℃) | |||||
Protection level | IP20 | |||||
dimension mm(W×H×D) | 600×1200×400 | 600×2200×600 | 800×2200×600 | |||
Non-standard sizes can be customized | ||||||
Weight(kg) | 150 | 200 | 400 |