High Voltage Electric Transformer Oil Purifier Machine Horizontal On Line Work
I. Transformer Oil Purification DescriptionI.
Our Transformer Oil Purifier Machine can improve the effect of de-acid, de-color and remove dielectric and acid more effectively and extend the lifetime of oils used in transformers and Reduce Maintenance Time for transformer.
The value of breakdown voltage will increase from 15KV to 65KV. The performance and lifetime of insulating oil will improve and extend awfully after purification and regeneration.
Customized requirements are available.
II.Transformer Oil Purification Parameters
1. Flow Rate: 600 liters/hour ~ 18000 liters/hour
2. Moisture content after purification: less than 4 PPM
3. Gas content after purification: less than 0.1%
4. Breakdown voltage after purification: more than 75 KV
III. Transformer Oil Purification Edges
1. High efficiency and effectiveness.
2. Enhance the value of breakdown voltage greatly.
3. Easy handling and maintenance.
4. Online work.
5. Lower maintenance and replacement expenses.
6. Small size, light weight, low noise
7. Various sizes and configurations (shield) available.
IV. Technical Specification of Vacuum Oil Purifier
Technical Specification | |||||||||
Item | Unit | VFD-30 | VFD-50 | VFD-80 | VFD-100 | VFD-150 | VFD-200 | VFD-300 | |
Flow Rate | L/H | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 18000 | |
Vacuum Range | Mpa | -0.092 ~ -0.099 | |||||||
Working Pressure | Mpa | ≤0.2 | |||||||
Max Vacuum Range | Pa | ≤50 | |||||||
Temperature Range | ℃ | 45 ~ 65 | |||||||
Breakdown Voltage | Kv | ≥75 | |||||||
Impurity Size | μm | ≤5 | |||||||
Dielectric Loss | Tg | ≤0.005 | |||||||
Interfacial Tension | mn/m | ≥40 | |||||||
Water Content | PPM | ≤4 | |||||||
Gas Content | % | ≤0.1 | |||||||
Power Supply | 380V/3P/50Hz(or as needed) | ||||||||
Working Noise | dB(A) | ≤72 | ≤78 | ||||||
Heating Power | Kw | 30 | 48 | 72 | 90 | 120 | 180 | 240 | |
Total Power | Kw | 35 | 54 | 77 | 98 | 129 | 189 | 254 | |
Pipeline Diameter | mm | DN25 | DN32 | DN32 | DN40 | DN50 | DN65 | DN65 | |
Net Weight | Kg | 550 | 850 | 1000 | 1100 | 1400 | 1600 | 2200 | |
Size | length | mm | 1500 | 1500 | 1700 | 1900 | 2100 | 2100 | 2600 |
width | mm | 1200 | 1200 | 1500 | 1400 | 1550 | 1550 | 1800 | |
high | mm | 1750 | 1750 | 1850 | 1800 | 1900 | 1900 | 2000 |
V. Available Style
1. Fixing type,mobile type with four wheels and mobile type with trailer.
2. Normal appearance type,shelf-covering type and explosion-proof type.
3. Avaliable in different color.
VI. Relative Series:
VFD series: Insulation oil purifier System specialize in purifying branded oil, insulation oil of high voltage and super high voltage transformer. Additionally, it is suitable for treating low viscosity lubrication oil.
TF series: Turbine oil purifier system is particularly suitable for purifying turbine lubricating oil. It also applys to treat hydraulic, coolant oil and other lubrication in which contain large of water, vapor, impurities, sludge, dielectric and colloid. It can eliminate them effectively and efficiently.
LV series: Lubrication Oil Filter System are suitable especially for purifying and restoring hydraulic oil, machine oil, coolant oil and various other lubrication oil.
GER series: Used oil regeneration system is suitable to regenerate used internal-combustion engine oil including diesel engine oil, gasoline engine oil, and used hydraulic oil, other used lubrication oil of machinery.
GED series: it is used to recycle all kinds of waste oil into base oil or diesel oil with high quality.