1800L/h High Dehydration Used Insulation Oil Double-Stage Vacuum oil Purifier
Double-Stage Vacuum Insulation Oil Purifier Technical Parameters:
Parameters | Value | |||||||
VFD-30 | VFD-50 | VFD-75 | VFD-100 | VFD-150 | VFD-200 | VFD-300 | ||
Capacity, liters/hour | 1800 | 3000 | 4000 | 6000 | 9000 | 12000 | 18000 | |
Heating Power, kW | 24 | 30 | 48 | 60 | 90 | 120 | 150 | |
Total Power, kW | 29 | 36 | 56 | 69 | 100 | 132 | 170 | |
Power supply | Fully Customizable | |||||||
Inlet Diameter, mm | 25 | 32 | 32 | 40 | 40 | 50 | 65 | |
Outlet Diameter, mm | 25 | 32 | 32 | 40 | 40 | 50 | 65 | |
Dimensions (without trailer) | length, mm | 1350 | 1500 | 1550 | 1900 | 2200 | 2400 | 2900 |
width, mm | 1100 | 1200 | 1250 | 1400 | 1500 | 1600 | 1800 | |
height, mm | 1700 | 1750 | 1800 | 1800 | 1850 | 1900 | 2000 | |
Weight(without trailer), kg | 600 | 800 | 900 | 1150 | 1500 | 1700 | 2400 | |
Processed Oil Spec | Water Content, ppm | ≤5 | ||||||
Dielectric Strength, Kv | ≥75 | |||||||
Filtration Fineness, um | ≤5( or 1-5 as needed ) | |||||||
Gas Content, % | ≤0.1 |
1800L/h Vacuum Insulation Oil Purifier Usage:
1.It can be used for oil filtering and oil filling on site for all kinds of oil-immersed transformer oil-immersed current and voltage transformer and high-voltage oil-less circuit breaker.
2. It can be used for hot oil cycle drying on site for the above equipment, especially for hot oil cycle drying on site for oil-immersed current and voltage transformer and high-voltage oil-less circuit breaker
3. It can also be used for the regeneration and purification of mildly deteriorated transformer oil, so that its performance reaches the qualified oil standard.
4. It can also be used in power plant, power station, power company, transformation industry, metallurgy, petrochemical machinery, transportation and railway industries
Other Optional for Transformer Oil/Insulation Oil:
VF series-- Single-Stage Vacuum Transformer oil Filtration machine.
VFD-R series-- Double-Stage Vacuum Black Insulation Oil Regeneration Machine