Specification
1 | Rated current | A | 630 | 630 | 1250 | 1250 |
2 | Circuit resistance at lowest rated contact force | μΩ | ||||
≤25 ≤20 | ||||||
3 | Rated short-circuit breaking current | KA | 20 | 25 | 20 | 25 |
4 | Breaking operations of rated short circuit breaking current | Times | 30 | |||
5 | Rated short-time withstand current | KA | 20 | 25 | 20 | 25 |
6 | Rated duration of short-circuit | S | 4 | |||
7 | Rated peak withstand current | KA | 50 | 63 | 50 | 63 |
8 | Rated short-circuit making current | KA | 50 | 63 | 50 | 63 |
9 | Rated breaking current of single capacitor bank | A | 630 | |||
10 | Rated breaking current of back-back capacitor bank | A | 400 |
Mechanical data
1 | Weight of movable parts | Kg | 0.52 |
2 | Closing force due to bellow and atmosphere | N | 80±25 |
3 | Force required to hold contacts open at full stroke | N | 150±40 |