18.5kw 25hp variable speed drive vsd for troque control heavy load application
VFD500 parameter distribution list:
Classification | Parameter group | Page |
Common parameters | 00:Basic function | Page 37 |
01:Frequency source selection | Page 39 | |
02:Start and stop | Page 45 | |
03:Ramp and S curve | Page 49 | |
04: Analog and pulse input | Page 51 | |
05:Analog and pulse output | Page 55 | |
06:Multi-function Digital input (DI) | Page 56 | |
07: Multi-function Digital output(DO) | Page 59 | |
08:Digital Output setting | Page 62 | |
Motor control | 10:Encoder type | Page 65 |
11:Motor1 parmeter | Page 66 | |
12:Motor1 VFcontrol parameter | Page 68 | |
13:Motor1 Vector controlparameter | Page 71 | |
14:Torque control | Page 73 | |
16:Energy saving control | Page 74 | |
Display and protection | 20:User-defined parameters | Page 75 |
21:Keypad and display | Page 77 | |
22:AC Drive configuration | Page 79 | |
23:Drive protection function setting | Page 81 | |
24:Motor protection parameter | Page 85 | |
25:Fault tracking parameter | Page 87 | |
26:Fault recording parameter | Page 87 | |
27:Monitoring parameter | Page 90 | |
Communication | 30:Modbus communication | Page 90 |
31:Canopen communication | Page 92 | |
Application | 40:Process PID Function | Page 92 |
41:Sleep function | Page 98 | |
42:Simple PLC | Page 100 | |
43:Programmable delay unit | Page 102 | |
44:Comparator and logic unit/controller | Page 104 | |
45:Multifunction counter | Page 108 | |
Motor 2 | 60:Motor2 basic parameter | Page 110 |
61:Motor2 parameter | Page 111 | |
62:Motor2 VF control parameter | Page 111 | |
63:Motor2 vector control parameter | Page 111 |
Energy saving control
16 Group Energy saving control | ||||
r16.00 | Electricity meter count (32BIT) | Unit:KW/H | - | ● |
r16.02 | Output power | Unit:0.1kw,output power will be negative in regen state | - | ● |
r16.03 | Power factor | -1.000~1.000 | - | ● |
P16.04 | Electricity meter zero clearing | 0:no function;1111:clear to zero | 0 | ☆ |
P16.05 | Energy saving control | 0:disable 1:enable | 0 | ★ |
P16.06 | Energy saving voltage limit | 0%~50%(0% means Energy saving control disable and more than 0% means Energy saving control enable | 0% | ☆ |
P16.07 | Energy saving filter time | 0.0~10.0s | 2.0s | ☆ |
Notice:P16.05 is invisible(it is useful in vf control) and When energy saving enabled, the output current can be reduced and thepower loss can be reduced when the load is light.For example, the fan and pump is light loaded, most of the inverters do not have this function, so we are more energy efficient. Energy savings can be achieved when it is light loads or load changes so slow |