Vertiv Liebert GXT5 UPS 8kVA/8kW 208V Online Rack Tower UPS GXT5-8000IRT5UXLE
Liebert™ GXT5 UPS is an online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. It protects critical equipment from all power disturbances due to blackouts, brownouts, saps, surges or noise interference. Scalable runtime option with matching auto-detection external battery cabinets offer additional flexibility when extended uninterrupted power is required. User friendly LCD interface as well as full network management capability, including configuration and remote updates, make this system easy to deploy and simple to maintain. With market leading efficiency and unity power factor operation, the Liebert™ GXT5 will fill your critical applications needs.
Technical Data
Power | |
---|---|
Output voltage regulation | 3% |
Output power factor | 1 |
Input power factor | 0.99 |
Output power | 8000 W |
Input operation voltage (min) | 176 V |
Input operation voltage (max) | 288 V |
Output operation voltage (min) | 230 V |
Output operation voltage (max) | 240 V |
Efficiency | 95% |
Emergency Power Off (EPO) | Yes |
Power factor | 1 |
Output power capacity | 8000 VA |
Efficiency (On-line mode) | 95% |
Single-phase input voltage supported | 220,230,240 V |
Battery | |
Battery type | VRLA |
Number of batteries supported | 16 |
Battery voltage | 12 V |
Battery capacity | 9 Ah |
Battery technology | Sealed Lead Acid (VRLA) |
Typical backup time at half load | 9.5 min |
Typical backup time at full load | 3.5 min |
Hot-swap battery | Yes |
Battery recharge time(90%) | 5 h |
Performance | |
UPS topology | Double-conversion (Online) |
Waveform | Pure sine |
Number of output phases | 1 |
Number of input phases | 1 |
Power protection features | Overload |
Noise level | 55 dB |
Audible alarm(s) | Yes |
Overload capacity (1 minute) | 150% |
Overload capacity (5 minute) | 125% |
Features | |
Output frequency | 50/60 Hz |
UPS topology | Double-conversion (Online) |
Waveform | Pure sine |
Output voltage regulation | 3% |
Number of output phases | 1 |
Number of input phases | 1 |
Output power factor | 1 |
Input power factor | 0.99 |
Output power | 8000 W |
Input operation voltage (min) | 176 V |
Input operation voltage (max) | 288 V |
Output operation voltage (min) | 230 V |
Output operation voltage (max) | 240 V |
Efficiency | 95% |
Emergency Power Off (EPO) | Yes |
Power protection features | Overload |
Power factor | 1 |
Noise level | 55 dB |
Audible alarm(s) | Yes |
Output power capacity | 8000 VA |
Overload capacity (1 minute) | 150% |
Overload capacity (5 minute) | 125% |
Efficiency (On-line mode) | 95% |
Single-phase input voltage supported | 220,230,240 V |
Input frequency | 50/60 Hz |
Ports & interfaces | |
USB port | Yes |
AC outlets quantity | 8 AC outlet(s) |
AC outlet types | C13 coupler,C19 coupler,IEC 320,Terminal |
Serial ports quantity | 1 |
RS-232 ports | 1 |
Design | |
International Protection (IP) code | IP20 |
Rack capacity | 5U |
Form factor | Rackmount/Tower |
Product colour | Black |
Safety | IEC62040-1:2008 |
Display | LCD |
Cooling type | Active |
Certification | CE, EMI/EMC/C-Tick EMC, ESD |
RoHS compliance | Yes |
Operational conditions | |
Operating temperature (T-T) | 0 – 40 C |
Storage temperature (T-T) | -15 – 40 C |
Operating relative humidity (H-H) | 0 – 95% |
Storage relative humidity (H-H) | 0 – 95% |
Operating altitude | 0 – 3000 m |
Technical details | |
Output voltage | 230 V |
Output frequency | 50/60 Hz |
Cooling | |
Cooling type | Active |
Weight & dimensions | |
Weight | 74.5 kg |
Width | 430 mm |
Height | 217 mm |
Depth | 630 mm |
Package width | 646 mm |
Package depth | 816 mm |
Package height | 520 mm |
Package weight | 93 kg |
Packaging data | |
Package width | 646 mm |
Package depth | 816 mm |
Package height | 520 mm |
Package weight | 93 kg |
Certificates | |
Safety | IEC62040-1:2008 |
Certification | CE, EMI/EMC/C-Tick EMC, ESD |
RoHS compliance | Yes |
Other features | |
Output voltage | 230 V |
Battery type | VRLA |