Unbalance Current Control Relay 220V 380V With Knob Setting Method With 4 LEDS
1
Features
Integrative structure Three-phase monitoring of overload, phase loss, phase unbalance Powered by the measuring circuit 1 NC SCR output contact 4 LEDs for status indication
2
Protective Functions
Overload,Phase loss,Phase unbalance
3
Typical Applications
Pumps . Fans, Blowers , Motors, Compressors
4
Approvals
• CE • CCC
5
Technical data
Type | JDB-1 |
Current range | 2.5-5A,4-10A,8-20A,16-40A,32-80A, 63-160A,150-300A |
Startup delay | 5s,10s,20s |
Protective functions | overload,phase loss,phase unbalance |
Setting method | by knob |
Indicators | ABC overload&phase loss |
Output contacts | 1NC(SCR output) |
Contact capacity | 1A 380VAC |
Operating voltage of control loop | AC220V or AC380V |
Dimensions(H*W*D) | 2.5-40A:38*90*63mm 80-300A:44.5*123*67mm |
Mounting | screw fixing |
Because the protector's output interface is a non-contact solid state AC electronic switch, so check the switch on and off characteristics can not use the multimeter's resistance file or pass-break measurement.
If the protector is used in the automatic control circuit and the protector is to be restarted after the action, the control circuit must be cut off to reset the output interface of the protector. Otherwise, the protector will be refused to start.
When the coil voltage of the AC contactor equipped with the interface of the protector is greater than 380V or the coil current is greater than 2A, an intermediate relay must be used as the conversion interface; otherwise, the protector will be damaged and the risk of accidents will occur.
The protector is not allowed to open the enclosure during use, and it is even more difficult to touch the live parts and terminals inside, otherwise there will be danger of electric shock; the terminal and the wire should be connected firmly; the length of the exposed part of the wire should be guaranteed not to cause phase Short-circuit the adjacent terminals, otherwise the protector may not work properly.
When the protector interface is used to connect or disconnect the load, its capacity cannot be greater than 4.4 times. Otherwise, the protector may be damaged and the risk of accident may occur. The protector cannot be used to control the DC contactor.
JDB-1 series motor protector is suitable for the control circuit of AC 45 ~ 60Hz, voltage 24V to 380V power supply circuit and AC contactor and other switch electrical appliances. When the main circuit of the motor has abnormal working conditions such as phase failure, overload, and three-phase unbalance, the protector can break the contacts of the switch electrical appliances in time, disconnect the three-phase power supply of the motor, and quickly and reliably protect the motor.