3 Phase Monitoring Relay JVM-A , Under Voltage Over Voltage Protection Relay
♦ Protective Functions
-- Phase sequence : refers to the fact that the order of the phases is not in the correct order of the zero value of the alternating current from the negative value to the positive value
-- Phase loss : Phase failure is a phenomenon in which one or more phases in the loop are disconnected, but not all phases lose voltage and no current. Or a phase voltage less than 60% of the rated voltage;
-- Overvoltage : the voltage (Umax-Ue)/Ue*100% exceeding the equilibrium potential of the electrode required for the discharge of ions on the electrode;
-- Undervoltage : the voltage required by the ion to discharge on the electrode is lower than the equilibrium potential of the electrode (Umin-Ue)/Ue*100%;
When the voltage phase sequence protector monitors the power supply voltage for any of the above-mentioned failures, the phase sequence voltage protector outputs a contact signal for the power control system to cut off the power supply to protect the device from damage.
1 . Phase loss and reverse phase protection <1S action
2 . Undervoltage protection delay range 1~10S adjustable
3 . Undervoltage protection range ± 5% ~ ± 20% adjustable
4 . Because this protector only protects against voltage and phase sequence, it can be applied to various power motors.
Undervoltage: means "not enough voltage." For all electrical equipment, there is a rated voltage, but in practice, it is not completely guaranteed to operate at rated voltage, which is a range near the rated voltage, and generally requires ±15%. In order to protect electrical equipment and process quality, if the voltage is lower than -15%, it is "undervoltage". When the operating voltage drops below this voltage, the protection action will be cut off. On the contrary, if the voltage is higher than +15%, it is “overvoltage” and the protection also acts to cut off the power.
Plug-in module with DIN socket
Three-phase monitoring of phase sequence, phase loss, over- and undervoltage Adjustable over- and undervoltage threshold and delay time , Powered by the measuring circuit , C/O contact , 2 LEDs for status indication
Apply to Pumps , Fans , Refrigeration Units , Blowers , Motors , Compressors , Lifts,Elevators , Cranes
Mining excavators and conveyors
♦ Approvals
• CE and CCC certain
♦ Technical data
Type | JVM-A |
Measuring circuit | 220VAC,380VAC50/60Hz |
Monitoring functions | phase sequence,phase loss,overvoltage,undervoltage |
Voltage setting range | ±5%~±20% |
Trip delay time | 1-10s adjustable |
Indicators | Power,Normal |
Output contacts | 1 C/O |
Contact capacity | 3A,250VAC |
Dimensions(H*W*D) | 61*49*70mm |
Mounting | DIN rail |
♦ Wiring Diagram