Wilo CronoLine IL E and Glanded Pump for Manufacturing and Processing Machinery
Company Info
Business Type: Trading Company
Business Range:Auto, Motorcycle Parts & Accessories, Bags, Cases & Boxes, Electrical & Electronics, Health & Medicine, Industrial Equipment & Components, Instruments & Meters, Manufacturing & Processing Machinery, Packaging & Printing, Service, Tools & Hardware
Management System Certification:ISO 9001
Main Products: Water Pump Set
Company Introduction:Tianjin Shiny-Metals Technologyco., Ltd., situated in Tianjin, China, is a professional enterprise specializing in pump research and development, design, production, sales, trade, and service. Currently, our products have been exported to over 40 countries and regions, consistently enhancing our global brand reputation. We manufacture a diverse range of pumps, including centrifugal pumps, axial flow pumps, jet pumps, submersible pumps, deep-well submersible pumps, and swimming pool pumps, spanning over 500 specifications. We have obtained the ISO 9001 certification from the International Organization for Standardization (CQC). Additionally, our civilian motors have undergone product evaluation for CCC China mandatory certification. Furthermore, we have achieved certifications such as CE, EMC, GS, RoHS, EAC, SASO, and ST. Our company fulfills customer needs with high-quality products, reasonable prices, and exceptional pre-sales, in-sales, and after-sales services. Adhering to the management principles of "quality first, customer first, and reputation-based", we are committed to providing global customers with the best water pump and water treatment system solutions, enhancing their quality of life. Our pursuit is "water makes the world a better place, we make water even better"
Product Description
Wilo CronoLine IL-E is an electronically controlled glazed single pump suitable for heating, cooling, and cooling systems. Flow range : < 590m³/h Lift range : ≤ 42m Permissible temperature range of -20 °C to +140 °C Nominal diameter DN 40 to DN 200 Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C Aplication field :Wilo CronoLine IL-E is mainly used for pumping heating water (compliant with VDI 2035), chilled water, and water ethylene glycol mixtures (non abrasive substances) in buildings. It plays a key role in heating, cooling, and cooling systems, ensuring efficient and stable water circulation in the system and maintaining comfortable indoor temperatures. |  |
Your advantages
- Energy savings due to integrated electronic power adjustment
- Optional interfaces for bus communication using plug-in IF-Modules
- Simple operation with Green Button Technology and display
- Integrated dual pump management
- Integrated full motor protection (PTC thermistor sensor) with trip electronics
|



Design
Electronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment
Application
The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.
Equipment/function
Operating modes
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- PID-Control
- Constant speed (n=constant)
Manual operation level
Manual functions
- Differential pressure setpoint setting
- Setting the speed (manual control mode)
- Setting the operating mode
- Setting the pump ON/OFF
- Configuration of all operating parameters
- Fault acknowledgement
External control functions
- "Overriding Off" control input
- “External pump cycling” control input (only effective in twin-head pump operation)
- Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
- Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
- Analogue input 0 – 10 V for actual value signal from pressure sensor
- Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
- Collective fault signal SSM
- Collective run signal SBM
Data exchange
- Infrared interface for wireless data exchange with IR-Stick
- Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
- Full motor protection with integrated trip electronics
- Access disable
Dual pump management (twin-head pump or 2 x single pumps)
- Main/standby operation (automatic fault-actuated switchover)
- Pump cycling main/standby operation after 24 hours
- Parallel operation
- Parallel operation (efficiency-optimised peak-load activation and deactivation)
-
Typekey
Example | IL-E 50/190-11/2-R1 |
IL-E | In-line pump with electronic control |
50 | Nominal diameter DN of the pipe connection |
190 | Nominal impeller diameter |
11 | Rated power P2 in kW |
2 | Number of poles |
R1 | Version without pressure sensor |
Technical data
- Permissible temperature range of -20 °C to +140 °C
- Mechanical seal for pumping water up to Tmax = +140 °C. Up to T ≤ +40 °C, a glycol admixture of 20 % to 40 % by volume is permissible. An alternative mechanical seal must be provided for water-glycol mixtures with a glycol content of > 40% to max. 50% by volume and a fluid temperature of > +40 °C to max. +120 °C or other fluids that differ from water. When using water-glycol mixtures, the use of an S1 variant with a corresponding mechanical seal is generally recommended.
- Mains connection
- 3~440 V ±10 %, 50/60 Hz
- 3~400 V ±10%, 50/60 Hz
- 3~380 V -5% +10%, 50/60 Hz
- Compliance with electromagnetic compatibility without additional measures:
- Interference emission for residential environment according to EN 61800-3:2018
- Interference immunity for industrial environments according to EN 61800-3:2018
- Protection class IP55
- Nominal diameter DN 40 to DN 200
- Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C
-
Materials
- Pump housing and lantern: EN-GJL-250
- Impeller
- Standard version: EN-GJL-200
- Special version: Bronze CuSn 10
- Special version: Stainless steel 1.4408
- Shaft: 1.4122
- Mechanical seal: AQEGG; other mechanical seals on request
-
Construction
Single-stage, low-pressure centrifugal pump in in-line design with
- Mechanical seal
- Flange connection
- Lantern
- Coupling
- Drive with integrated electronic speed control
-
Scope of delivery
- Pump
- Installation and operating instructions
-
Options
- …-R1 variant without differential pressure sensor
- …-L1 variant with bronze impeller (at additional charge)
- …-L4 variant with stainless steel impeller (at additional charge)
-
Accessories
- 3 Mounting brackets with fixation material for installation on a base
- Wilo-IR-Stick
- IF-Module PLR for connecting to PLR/interface converter
- IF-Module LON for connection to the LONWORKS network
- IF-Module BACnet
- IF-Module Modbus
- CAN IF-Module
- VR-HVAC control system
- Control system CCe-HVAC
- Control system SCe-HVAC
- Differential pressure sensor (DDG)