The WT-2 Voltage Regulator is an encapsulated unit contained in a plastic case.The regulator controls the dc exciter field power of conventional, 50 or 60 Hz brushless generators that have a max 63 Vdc exciter field to regulate the generator output voltage.Regulation is provided by sensing the generator
output voltage, converting it to a dc signal and comparing the signal to a reference voltage signal.
An error signal is developed and used to control the dc field power in order to maintain a constant
generator output.
Output Power(DC)
6 A at 63 Vdc maximum continuous with a 240
Vac input.
Max Output Current(DC)
15 A maximum, 1 minute
Exciter Field DC Resistance
6.0 ohms minimum.
Input(AC)
180 to 300 Vac, single-phase, 50/60 Hertz.
Burden: 1000 VA maximum at 240 Vac power.
Sensing Voltage(AC)
180 to 277 Vac at 220 Vac single-phase system;312 to
480 at 400 Vac three phase system, 50/60 Hertz.
Burden: 5 VA.
Voltage Adjust Range
180 to 277 Vac using the internal voltage adjust.
The external voltage adjust provides a ±10%
Regulation Accuracy
Plus/minus 0.5%.
Voltage Drift
<±1% voltage variation for a 50°C (90°F) change.
Response Time
<1 cycle
Voltage Build-Up
Internal provisions for automatic build-up from
generator residual voltages as low as 9 Vac at 35 hertz.
Power Dissipation
40 W maximum.
Paralleling Provisions
CT input for customer supplied 1 Amp nominal CT.
Adjustable droop from 0 to 5% with 5 Amps input at 0.8
power factor.
Operating Temperature
-25ºC ~ +60ºC.
Vibration
Withstands 1.2 Gs at 5 to 26 Hz; 0.036" double
amplitude at 27 to 53 Hz; 5 Gs at 53 to 1000 Hz.
Withstands up to 15 Gs in each of three mutually
perpendicular axes.
Weight
0.4 kg net.