Specifications
Brand Name :
WINLEY
Model Number :
S-2500/13
Certification :
UL,CE,ISO
Place of Origin :
CHINA
MOQ :
1unit
Price :
$5000-$150000
Payment Terms :
T/T
Supply Ability :
1000set/month
Delivery Time :
30days
Packaging Details :
Plywood case
Phase :
Three Phase
Capacity :
2500KVA
Primary Voltage :
13200V
Secondary Voltage :
480Y/277
Vector Group :
DYN1
Temperature Rise :
65°C
Impedance (Typical) :
5.75%
Frequency :
60 Hz
Description

Three Phase Pad Mounted Transformer distribution power substation 13200V to 480V 2500 Kva

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Performance

1) The structure is compact and reasonable, and the volume is small, which is only about one-third of the European-style box change of the same capacity;
2) Fully sealed, fully insulated structure, no need to set up safety barriers, and reliable guarantee for personal safety;
3) There are a variety of power supply schemes for users to choose from, which can adopt terminal power supply and realize ring network or dual power supply;
4) S11 oil-immersed power transformer is adopted, which has low loss, low temperature rise and strong overload capacity;
5) Double fuses (backup protection fuse + plug-in fuse) are used for protection, and the plug-in fuse fuse has the current and temperature dual sensitivity characteristics to ensure the safe and reliable operation of the product;
6) The 200A cable connector can be plugged and unplugged under load, and can be operated as a load switch in an emergency. It also has the characteristics of an isolating switch.
7) The winding adopts Dyn11 connection and the iron core adopts a three-phase four-column structure, so that the product can run under any asymmetric load, and the neutral point does not drift, the voltage is stable, the power supply quality is high, the cabinet heats up, the noise is low, and the lightning protection performance is good ;
8) The cabinet adopts anti-corrosion design and special spray paint treatment, beautiful and novel, suitable for various environments, and achieve the effect of beautifying the city.

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Main data

Phase Three Phase
Capacity 2500 KVA
Vector Group YnD1
Primary Voltage 480Y/277
Primary Voltage Class 1.2 kV Class
Primary Phasor Wye-N
Primary BIL 30 KV
Secondary Voltage 13200GrdY/7620
Secondary Voltage Class 15 kV Class
Secondary Phasor Grounded Wye
Secondary BIL 95 KV
Frequency 60 Hz
Temperature Rise 65°C
Insulation Rating Class E Insulation - 120°C, 248°F
Cooling Class KNAN; Self-Cooled
Impedance (Typical) 5.75%
Load Break Switch Rating 200-Amp, 15 kV
Load Break Switch Location High Voltage (HV) Front Compartment
Efficiency Standard(s) Meets DOE 2016 Standards, Meets ANSI/IEEE Standards
K-Factor Rating (Harmonic Mitigation) K-1 (Standard)
Winding Material Copper
Ambient Temperature Rating 40°C
Sound Level 61 dBA
Elevation Rating 3300ft (1000 meters) Above Sea Level
Core Material Grain Oriented Steel
Tank Material Coated Steel
Dry Weight (w/o Oil)* 4,566 lb
Total Weight (Liquid Filled)* 10,567 lb
Efficiency % 99.10%
No Load Loss (in watts)) +/- 2,100W
Full Load Loss (in watts) at 100% +/- 14,500W

Feature


• 60 Hz operation.
• 65°C average winding rise.
• Radial & loop feed arrangements.
• Dead and live front type of HV terminals.
• HV BIL 45 – 150 kV (Dead Front) 200 kV (Live Front).
• LV BIL 30 – 60 kV.
• Three-point latching of low-voltage door.
• High-voltage door, which can be opened only after
the low-voltage door is opened.
• Rigid steel partition.
• Transformer tank welded from cover to base.
• Permanent nameplate.
• One-inch NPT pipe cap filling provision.
• ANSI tank ground pads.
• One-inch drain valve and sampler.
• Automatic pressure-relief valve (35 SCFM).
• Tap changer with (2) 2.5% full capacity taps above
and below nominal.
• One 10”x18” (or 14”x25”) hand hole in transformer
tank cover.
• Painted olive-green color (Munsell 7GY 3.29/1.5).
• Designed, manufactured and tested in accordance
with the latest ANSI standards

Specification

Rated Power (KVA) High Voltage (KV) Low Voltage (V) Loss (W)
No-load Loss (W) On-load Loss (W)
75KVA 24.94/14.4kV
12.47/7.2kV
34.5KV/
19.92KV/
13.8KV/
13.2KV/
or others
120/240V
480Y/
277V
600Y/
347V
180 1250
112.5KVA 200 1500
150KVA 280 2200
225KVA 400 3050
300KVA 480 3650
500KVA 680 5100
750KVA 980 7500
1000KVA 1150 10300
1500KVA 1640 14500
2000KVA 2160 20645
2500KVA 2680 23786
3000KVA 3300 25300
3750KVA 4125 27875
5000KVA 5200 30000

Technical drawings

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Production process

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

FAQ

1. Q: Can I have a sample order?

A: Yes, we welcome sample order to test and check quality.

2. Q: What is the lead time?

A: Mass production time 15-25 days.

3. Q: How long is the warranty?

A: 24 monthes from B/L. If there are any accessory problems,just provide the photos of damaged accessory,then we will provide free service. According to the number of products,we will provide easily damaged accessories for free. we also can provide technical support if you need.

4. Q: Is OEM/ODM available?

A: Yes,it is! We are manufacturer with our own R&D team, we can customize products according to customer's drawing or requirements.

Customized services:

a. Customized color and special function.

b. Customized box.

c. Print customer's logo.

d. Your other ideas about product, we can help you design and put them into production. The above customized services must be confirmed before production.

5. Q: How to control the products quality?

A: Our company owns the core technology ,all kinds of products hold CE certificate. We have professional engineers. Workers are strictly required to make products according to the drawings. Each process has technical instructors.The QC supervisors will regularly inspect the production. We will do products performance tests during production, and comprehensive quality tests when the products is completed.

Send your message to this supplier
Send Now

Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Ask Latest Price
Watch Video
Brand Name :
WINLEY
Model Number :
S-2500/13
Certification :
UL,CE,ISO
Place of Origin :
CHINA
MOQ :
1unit
Price :
$5000-$150000
Contact Supplier
video
Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva
Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva
Three Phase Pad Mounted Transformer Distribution Substation 13200V To 480V 2500 Kva

Xiamen Winley Electric Co.,Ltd

Verified Supplier
4 Years
fujian, xiamen
Since 2007
Business Type :
Manufacturer, Seller
Total Annual :
$15M-$20M
Employee Number :
50~70
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement