Input
Input signal: PT100, Cu50, Ni1000 and other thermal resistance; B, E, J, K, N, R, S, T and other thermocouples; voltage (maximum range 0-10V); millivolts (maximum range 0-100mV); Current source (4- 20mA); transmitter (distribution), current 4-20mA; resistor, potentiometer (maximum range 0-2K)
Distribution voltage: ≥16V
Measuring range: depending on the type of sensor used
Output
Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V
Output load resistance: RL ≤ 500Ω (when the output is a current signal); RL ≥ 10KΩ (when the output is a voltage signal)
Basic parameters
Power supply: DC24V, ±10%
Current consumption: ≤50mA (one input and one output 24V power supply, 20mA output); ≤70mA (one input and two output, 24V power supply, 20mA output)
Basic accuracy: 0.1% F.S.
Response time: 0.5S
Insulation strength: 1500V AC / 1min (between input, output, and power)
Insulation resistance: ≥100MΩ (between input, output, and power)
Operating temperature range: -20~+55 degrees
Electromagnetic compatibility: in accordance with GB/T 18268 (IEC61326-1)
Parameter | ||||
THS-TP | X | X | X | marks |
Configuration | 1 | 1 input 1 output | ||
2 | 1 input 2 output | |||
Input signal | U | General signal input (RTD, TC, Potentiometer) Please indicate signal type and measure range | ||
Output signal | 1 | 4-20mA | ||
2 | 0-20mA | |||
4 | 0-5V | |||
6 | 0-10V | |||
Please indicate your required input type and output type when place order |
Dimension
How to wire