Input
Input signal: 4-20mA; 0-20mA
Maximum input current: 25mA
Distribution voltage: ≥21VDC
Input impedance: ≤25Ω
Output
Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V
Maximum output current: 25mA
Output load resistance: RL ≤ 800Ω (output is current signal); RL ≥ 1MΩ (output is voltage signal)
Output ripple: ≤10mVp-p
Basic parameters
Number of channels: two in and two out (THS-IP5XX)
Power supply: DC24V, voltage range: DC20~40V
Current consumption: ≤93mA (two in and two out, 24V power supply, power distribution input, 20mA output, load resistance = 550Ω)
Basic accuracy: ±0. 1%F.S
Temperature drift: typical value ≤ ± 1uA / 10 degrees
Response time: ≤10mS (0-90%) (TYP)
Power-on stabilization time: ≤1S
Insulation strength: 2500VAC / 1 minute (between input, output and power)
Insulation resistance: ≥100MΩ (between input, output, and power)
Operating temperature range: - 20~+55 degrees
Electromagnetic compatibility: in accordance with GB/T 18268 (IEC61326-1)
Suitable for field devices: two-wire transmitter, current source.
Parameter | ||||
THS-IP | X | X | X | marks |
Configuration | 1 | 1 input 1 output | ||
2 | 1 input 2 output | |||
Input signal | 1 | 4-20mA | ||
2 | 0-20mA | |||
Output signal | 1 | 4-20mA | ||
2 | 0-20mA | |||
4 | 0-5V | |||
6 | 0-10V | |||
Please indicate your required input type and output type when place order |