Wireless Modbus RTU for Stacker/Reclaimer Remote Control
This application is widely used for PLC wireless collect 4-20mA signal and PLC remote control stacker and reclaimer.
Introduction
You could refer the diagram, our wireless RTUs are used to help build wireless communication between stacker and reclaimer machine with its control room. This will reduce much cost and minitor, maintain time.
Here we use LS-RDIO0202+LS-RAI/O expanders, users can get the 4-20mA analog signal and ON-OFF condition of machine in time.
Data sheet of LS-RAI/O02
Frequency | 433MHz or 450MHz or 470MHz |
Power output | 1W |
Products | 2AI |
Input type | 4-20mA or 0-5V or 0-10V |
Output type | 4-20mA or 0-5V or 0-10V |
Resolution ratio | 24 bit |
Accuracy | ±0.02% |
Power supply | 9-36V DC usually use 24V DC |
Interface | RS-485 |
Channel No. | 16ch default, can program via DIP switch |
Antenna | Sucker antenna with 1.5m cable |
Working temperature | -35 °C ~ +75 °C industrial |
Working humidity | 10%-90% relative humidity, no condensation |
Dimension | 115×90×40(mm) |
Fix way | Standard 3.5 inch industrial DIN guild rail |
Data sheet of LS-RDIO0202
Parameter | |
Power output: | 1W (or 100mW version) |
Power supply: | 9V-30V (usually choose 24V DC or 12V DC) |
Control distance: | 3km (or 1km version) |
Baud rate: | 1200bps |
Receiving sensibility: | -123dBm@1200bps, -118dbm(9600bps) |
Networking | |
Networking: | Point to point and point to multipoint |
Protocol: | Modbus RTU protocol |
Port Description | |
Input: | 2 active inputs (passive customize), isolated |
Output: | 2 passive relay outputs, isolated contact max load AC250V/5A,DC30V/5A (active outputs 0-5V customize) |
Communication port | RS485 (wireless RS485 customize) |
Current | |
Transmit current: | <600mA (or 100mA version) |
Receiving current: | <50mA (or 20mA version) |
General | |
Frequency: | 433MHz, 400, 450, 470 or other band |
Channel No: | 16 channels, can change via DIP switch |
Physical Properties | |
Dimension: | 115×90×40(mm) |
Antenna Connector: | SMA,vehicle antenna with 1.5m cable |
Temperature: | -35℃~+75℃( industrial) |
Mounting method: | Standard 3.5 inch industrial guild rail |
In control room, the PLC can get reclairmer's analog signal by wireless and control the ON-OFF condition. It's easy to operate.
OK, welcome to try our goods!