Introduction
The information provided in this manual covers the Master and Slave fire alarm control panel. The panel range is designed to
meet the requirements of EN54 Parts 2 & 4.
The fire alarm control panels (2 Zones) provide all of the sophisticated features required of a leading edge conventional fire
alarm system along with the simple operation and efficient installation methods demanded by both installers and building
users.
A comprehensive range of auxiliary devices is available to operate with the fire control panels including optical, ionization,
photoelectric, photoelectric-thermal and heat detectors.
Each of the system components has been specifically designed to operate as part of the system. This provides assurance
that the control panel, smoke detectors, interface devices and the ancillary components are all fully compatible with one
another and that the full range of system functionality is supported by each device.
Product Features 4 conventional input zones.
Each zone can be connected with 30 conventional fire detectors. Each panel has external devices control output points, Through the points, the panel can control such external devices as bell, siren, flame detector, beam detector etc.
Dedicated alarm and trouble relays.
1 RS485 can be able to connect the other panel.
Housed in a 370mm W x 440mm H x 100mm D metal enclosure.
Enclosure supports 1 12V, 4.5Ah backup batteries.
The panel can be used independently or connect by RS485.
Specification
Primary AC | 120VAC 50/60 Hz Power supply rating |
240VAC 50/60 Hz |
Power supply rating | 2 Amps @ 24VDC |
Maximum Battery Charging Current | 0.90 Amps @ 26VDC |
Initiating Device Circuits Zones | Alarm Zone 2/4/8/16 |
Normal Initiating Operating Voltage | 22VDC, Maximum 26VDC, regulated |
Normal Monitor Current | <50mA |
Alarm Current | <150 mA |
Short Circuit Initiating Current (per zone) | 35mA Maximum |
Maximum Initiating Resistance (per zone) | 10 ohms |
Initiating End-of-Line Resistor | 4K7 ohms, 1/2W 5% |
Standby Detector Current (per zone) | 4mA maximum |
Maximum Detector Count (per zone) | 30 detectors |
Initiating Cabling Type | 18AWG Twisted Shielded pair (14 – 18 AWG) |
Detector Base Impedance | 430 ohms |
Fault Relay rating | 2A & 30VAC, resistive |
Alarm( Auxiliary ) Relay rating | 2A & 30VAC, resistive |