YJV8.7KV XLPE Insulated PVC Sheathed Cable / Low Voltage Power Cable
Insulated PVC Sheathed Cable Construction
1. Construction:Copper/aluminum/solid/stranded round conductor
2. Conductor screen:Semi-conducting polymer
3. Insulation:XLPE insulation
4. Insulated screen:Semi-conducting polymer
5. Metal screen:Copper tape or copper wire
6. Overall cable sheath:PVC/PE
Insulated PVC Sheathed Cable Applications
Insulated PVC Sheathed Cable is used indoor or outdoor, in tunnel, cable furrow or pipe, to be laid underground, be applicable to the well, water inside and fall in the bad soil.
Standards
International: IEC 60502, IEC 60228
China: GB/T 12706.2-2008 IEC60502.2 HS620 S1
Other standards such as BS,VDE and ICEA upon request
Technical data
Rated voltage: 8.7 kV
Maximum Conductor Temperature: under normal (90 ℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp.: The cable shall be pre heated if the ambient temperature is below 0℃
Min. Bending Radius: single core cable 20(d+D)±5%
Multi-core cable 15(d+D)±5%
Insulated PVC Sheathed Cable Technical Specifications
Nom. Cross-section of conductor | Strands No./Dia. Of Conductor | Insulation Thickness | Thickness of Copper Strip | Sheath Thickness | Approx. O.D. | Approx. | Max. D.C Resistance of Conductor (20 ℃) | Testing Voltage A.C | Current Rating | |
Weight | In air (A) | In soil(A) | ||||||||
1×25 | 7/2.17+0.01 | 5.5 | 0.12 | 1.8 | 24.9 | 771 | 0.727 | 48 | 165 | 160 |
1×35 | 7/2.56+0.01 | 5.5 | 0.12 | 1.8 | 25.9 | 890 | 0.524 | 48 | 205 | 190 |
1×50 | 19/1.86+0.01 | 5.5 | 0.12 | 1.8 | 27.2 | 1044 | 0.387 | 48 | 245 | 225 |
1×70 | 14/2.56+0.01 | 5.5 | 0.12 | 1.8 | 28.9 | 1285 | 0.268 | 48 | 305 | 275 |
1×95 | 19/2.56+0.02 | 5.5 | 0.12 | 1.9 | 30.7 | 1584 | 0.193 | 48 | 370 | 330 |
1×120 | 24/2.56+0.02 | 5.5 | 0.12 | 1.9 | 32.2 | 1849 | 0.153 | 48 | 430 | 375 |
1×150 | 30/2.56+0.01 | 5.5 | 0.12 | 2.0 | 33.8 | 2153 | 0.124 | 48 | 490 | 425 |
1×185 | 37/2.56+0.02 | 5.5 | 0.12 | 2.0 | 35.6 | 2557 | 0.0991 | 48 | 560 | 480 |
1×240 | 48/2.58+0.02 | 5.5 | 0.12 | 2.1 | 38.0 | 3161 | 0.0754 | 48 | 665 | 555 |
1×300 | 60/2.58+0.02 | 5.5 | 0.12 | 2.2 | 40.4 | 3790 | 0.0601 | 48 | 765 | 630 |
1×400 | 60/2.93+0.02 | 5.5 | 0.12 | 2.3 | 43.5 | 4712 | 0.047 | 48 | 890 | 725 |
1×500 | 60/3.33+0.02 | 5.5 | 0.12 | 2.4 | 46.9 | 5747 | 0.0366 | 48 | 1030 | 825 |
1×630 | 60/3.76+0.02 | 5.5 | 0.12 | 2.5 | 50.5 | 7129 | 0.0283 | 48 | 1200 | 950 |
3×25 | 7/2.17+0.01 | 5.5 | 0.10 | 2.6 | 50.5 | 2629 | 0.727 | 48 | 120 | 125 |
3×35 | 7/2.56+0.01 | 5.5 | 0.10 | 2.6 | 52.7 | 3020 | 0.524 | 48 | 140 | 155 |
3×50 | 19/1.86+0.01 | 5.5 | 0.10 | 2.7 | 56.1 | 3564 | 0.387 | 48 | 165 | 180 |
3×70 | 14/2.56+0.01 | 5.5 | 0.10 | 2.8 | 60.0 | 4370 | 0.268 | 48 | 210 | 220 |
3×95 | 19/2.56+0.02 | 5.5 | 0.10 | 3.0 | 63.8 | 5344 | 0.193 | 48 | 255 | 265 |
3×120 | 24/2.56+0.02 | 5.5 | 0.10 | 3.1 | 67.3 | 6231 | 0.153 | 48 | 290 | 300 |
3×150 | 30/2.56+0.01 | 5.5 | 0.10 | 3.2 | 70.5 | 7190 | 0.124 | 48 | 330 | 340 |
3×185 | 37/2.56+0.02 | 5.5 | 0.10 | 3.3 | 74.6 | 8516 | 0.0991 | 48 | 375 | 380 |
Ordering Advice
Rated Voltage
Application Standard: IEC/BS/UL/GB
Number of Cores
Conductor Size & Construction
Type of Insulation
Armored or unarmored. If armor, the armor type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
PACKING AND SHIPPING
We are capable of meeting the strictest delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self-adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.