TUV Standard 2.5mm2 4mm2 6mm2 PV1-F DC1500v Solar power PV Cable
Product Description
Applications
These cables are designed for connecting photovoltaic system components inside and outside of buildings and equipment with high mechanical requirements and extreme weather conditions.
Standards
DIN EN 50618 (H1Z2Z2-K)
Approvals:
TÜV EN50618 H1Z2Z2-K
Product features:
1. Rated Voltage: DC 1500V
2. Ambient Temperature: -40ºC--90ºC Max. Temperature at Conductor 120ºC:
3. Conductor: Tin-Plated copper, Class5
4. Insulation: 125ºC XLPE
5. Jacket: 125ºC XLPE
6. Color: Black
7. Marking: FRCABLE TÜV EN50618 H1Z2Z2-K DC 1.5KV, 1X4.0mm2 Meter marking
3 Application:
Specifically designed for connecting photovoltaic system components inside and outside of building and equipment with high mechanical requirements and extreme weather conditions For permanent installations.
4 General characteristic
Cable made of electron-beam cross-linked insulation and coating; high resistance against heat, cold, oil, abrasion, ozone, UV and weather; with improved reaction in case of fire .
1. Double insulation,electron beam cross-linked
2. Excellent resistance to UV, water, ozone, fluids, salt, general Weathering
3. Excellent resistance to abrasion
4. Halogen free,flame retardant,low toxicity
5. Excellent flexibility and stripping performance
6. High current carrying capacity
7. TUV and UL approved
Specification:
Cross Section (mm²) |
Conductor Construction (n/mm) |
Conductor Stranded OD.(mm) |
Insulation Min.Wall Thickness(mm) |
Sheath Min.Wall Thickness(mm) |
Cable OD.(mm) |
Conductor Max.Resistance AT20°C (Ω/km) |
Current Araaing Capacity AT 60°C(A) |
1.5mm² | 30/0.25 | 1.58 | 0.67 | 0.73 | 4.90 | 13.3 | 30 |
2.5mm² | 50/0.25 | 2.02 | 0.67 | 0.73 | 5.45 | 7.98 | 41 |
4mm² | 56/0.30 | 2.60 | 0.67 | 0.73 | 6.10 | 4.95 | 55 |
6mm² | 84/0.30 | 3.42 | 0.8 | 0.80 | 7.20 | 3.30 | 70 |
10mm² | 142/0.30 | 4.56 | 0.9 | 0.90 | 9.00 | 1.91 | 98 |
16mm² | 228/0.30 | 5.60 | 1.00 | 0.90 | 10.20 | 1.21 | 132 |
PHOTOFLEX Photovoltaic Cable
Conductor | Stranded tinned copper conductor per DIN VDE 0295 and IEC 60228 Class 5. |
Insulation | Electron beam cross-linked, halogen free and flame retardant compound. |
Sheath | Electron beam cross-linked, LSZH and flame retardant compound, Black. |
Rated Voltage U0/U | 1/1 kV AC; 1.5/1.5 kV DC |
Maximum Permitted DC Voltage | 1.8 kV DC (conductor/conductor, non earthed system, circuit not under load) |
Insulation Resistance | 1000 MΩ-km |
Spark Test | 6000 Vac (8400 Vdc) |
Voltage Withstand |
6500 Vac for 5 minElectron |
Maximum Voltage | 1.2KV (AC), 1.8KV (DC) |
Ambient Temperature | -40ºC ~ +90ºC |
Maximum Temperature At Conductor | 120ºC (20000h) according to IEC/EN 60216-1 |
Short Circuit Temperature | 200ºC/5 sec |
Thermal Endurance Test | According to EN 60216-2 (temperature index +120° C) |
Damp-Heat Resistance | According to EN 50618, Table 2with 85% humidity(test acc. to EN 60068-2-78) |