11kv Sheathed Copper Conductor Medium Voltage Power Cable Wire Screened/XLPE Insulate
Applications:
11kv Sheathed Copper Conductor Medium Voltage Power Cable Wire Screened/XLPE Insulate are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
Standard:
Single Core Cables to BS 6622/BS 7835/IEC 60502/VDE 0276
Conductor Screen
This will be an extruded layer of semi-conducting crosslinkable compound applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen. The triple extrusion is a single high precision operation that eliminates the possibility of any contamination between the layers which could create irregularities in the electrical field.
Insulation
This will be an extruded layer of XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.
Insulation Screen
This will be a layer of semi-conducting crosslinkable compound which will be applied by triple extrusion process over the insulation.
Metallic Screen
It will consist of a layer of copper tape applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer ’s requirement can also be provided on request. Copper wire screen's nominal cross sectional area can as per customer's actual requirement.
Over Sheath
An extruded layer is applied over the armour in case of armoured cables and over laid up cores in case of unarmoured cables. Outer sheath material can be either PVC, PE, HDPE or MDPE. our
medium voltage cables are normally supplied with red PVC over sheaths complying with BS 6622 or IEC 60502. Other colors may be provided to suit a range of installation considerations such as the effect of UV radiations and differing soil compositions. Anti-termite formulations can also be supplied in addition to graphite-coated over sheaths where on-site testing of the sheath is required
11kv Sheathed Copper Conductor Medium Voltage Power Cable Wire Screened/XLPE Insulate
Parameters:
Nom. Cross- Section Area | Nom. Insulation Thickness | Metallic Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
mm² | mm | mm² | mm | mm | kg/km |
50 | 8 | 16 | 2 | 31.1 | 960 |
70 | 8 | 16 | 2 | 32.9 | 1090 |
95 | 8 | 16 | 2.1 | 34.8 | 1240 |
120 | 8 | 16 | 2.1 | 36.8 | 1360 |
150 | 8 | 25 | 2.2 | 38.6 | 1510 |
185 | 8 | 25 | 2.2 | 40.4 | 1680 |
240 | 8 | 25 | 2.3 | 43.7 | 1980 |
300 | 8 | 25 | 2.4 | 45.9 | 2250 |
400 | 8 | 35 | 2.5 | 49.3 | 2640 |
500 | 8 | 35 | 2.6 | 52.6 | 2965 |
Product show:
Why Choose Zhenglan Cable:
Medium voltage cables are manufactured using the monosil process. We provide the highly specialized plant, state-of-the-art research facilities and meticulous quality control procedures that are required for the manufacturing of PVC insulated cables for use up to 6KV and XLPE/EPR insulated cables for use at voltages up to 35 KV. The materials are all kept in cleanliness-controlled conditions throughout the production process in order to ensure the absolute homogeneity of the finished insulation materials.