1kv 1x35sqmm aluminum core xlpe insulated UV resistant pvc sheathed single core power cable unarmored IEC 60502-1
Applications:
These cables are used for electricity supply in low voltage installation system. Such as high rise buildings and apartments, airports, shopping centres, cinemas and road and rail tunnels. And tall building, Hospital, Theatre, Power station, Metro Tunnel or Petrochemical Industry or other special place required for low smoke , zero halogen clean and safe cable.
Construction:
Conductors:Copper or Aluminium conductor, round standed or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Noted: Insulation color as per standards or customer requirement.
Standard:
Basic design to IEC 60502-1, IEC 60228,BS EN 60228
China: GB/T 12706.2-2008
Other standards such as BS7870,DIN and ICEA upon request
Certificates:
CE, ROHS,KEMA and more others at request
Insulation:
PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346. PVC material shall be Type A as per IEC 60502-1 or TI1 as per BS EN 50363.PVC Insulation material as per SASO 1694 rated for 85°C continuous operation is also available upon special request.
Colour Code Colour Code (1):
1 Core: Red or Black; 2 Cores: Red, Black; 3 Cores: Red, Yellow, Blue; 4 Cores: Red, Yellow, Blue, Black; 5 Cores: Red, Yellow, Blue, Black, Green; Above 5 Cores: Black Cores with White numerals
Outer Sheath: Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSF, CPE are available on request.
Fire Performance of Cable Sheaths: Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.
Cable Parameters:
Conductor dimensions (mm2) | Insulation thickness (mm) | Nonmetallic sheath, unarmored cable | |||
Sheath thickness | Outer diameter (approximate) | Cable weight (Kg/km) | |||
mm | mm | Copper core | Aluminum core | ||
1C | 1C | 1C | 1C | ||
1.5 | 0.7 | 1.4 | 5.6 | 45 | 35 |
2.5 | 0.7 | 1.4 | 6 | 57 | 42 |
4 | 0.7 | 1.4 | 6.5 | 75 | 50 |
6 | 0.7 | 1.4 | 7 | 97 | 60 |
10 | 0.7 | 1.4 | 8.1 | 143 | 80 |
16 | 0.7 | 1.4 | 9.2 | 206 | 106 |
25 | 0.9 | 1.4 | 10.6 | 303 | 146 |
35 | 0.9 | 1.4 | 11.8 | 403 | 185 |
50 | 1 | 1.4 | 13.2 | 554 | 241 |
70 | 1.1 | 1.4 | 15 | 755 | 317 |
95 | 1.1 | 1.5 | 16.9 | 1004 | 409 |
120 | 1.2 | 1.5 | 18.5 | 1250 | 498 |
150 | 1.4 | 1.6 | 20.6 | 1558 | 619 |
185 | 1.6 | 1.6 | 22.7 | 1908 | 750 |
240 | 1.7 | 1.7 | 25.3 | 2450 | 947 |
300 | 1.8 | 1.8 | 27.9 | 3043 | 1163 |
400 | 2 | 1.9 | 31.6 | 4021 | 1514 |
500 | 2.2 | 2 | 35 | 5002 | 1869 |
Productos show:
Why Choose Us: