CU/XLPE/SWA/PVC Low Voltage Power Cable 4 Core 16mm2 PVC Jacket
Application
To be laid directly in ground, water, outdoors, indoors and in cable ducts e.g. in industrial and switchboard plants.
Construction
1 ..... stranded bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... semi-conducting tape
6 ..... screen of copper wires
7 ..... Fillers strip, Yarn, or Paper
8 ..... Non woven Wrapping tape or Flame Retardant
9 ..... Extruded PVC Inner Covering
10 .... Galvanized Steel Tape Armoured
11 .... Overall Sheath: polyvinylchloride (PVC) or FR-PVC, PE, LSOH
Standards
IEC 60502, 60228, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -20°C till +90°C | |
fixed | -20°C till +90°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 50265-2-1 |