These cables are designed for 400 Hz systems for power supply of aircraft, computer systems and radar stations, suitable for laying in earth, in water, outdoors, indoors and in cable ducts.
VDE 0295
Conductor: Stranded bare copper conductor, Class 2 or 6 to VDE 0295/IEC 60228.
Insulation: PVC/XLPE. TP RUBBER acc. to EN 50363-5
Outer Sheath: PVC. Polyolefin / TP RUBBER acc. to EN 50363-5
35 mm² Extra flexible conductor acc. to IEC 60228,6
-- Wires in conductor, bare: 1029 - Pcs.
-- Wire diameter : 0,20 ± 0,04 mm
-- Resistance : 0,546 +0,006 Ω/km
-- ay length Rope lay
-- Copper weight : 305 Kg/km
Insulation of 35mm² acc. to EN 50363-5
-- Material XLPE 90°C
-- Temperature range -45 to +90 °C
-- Wall thickness 1,2 + 0,2 mm
-- Outer diameter 10,6 + 0,4 mm
-- Color Light Blue, 2xBlack, 2xBrown, 2xWhite
Outer sheath acc. to EN 50363-8
-- Properties Nominal value Tolerance Unit
-- Material TP Rubber
- - Temperature range -30 to +80 °C
-- Wall thickness 3,1 ± 0,5 mm
-- Outer diameter 42,8 ± 2,0 mm
-- Color Black
Rated Voltage Uo/U (Um) | 600/1000V |
Operating Temperatures | -20℃~+70℃ |
Minimum Bending Radius | static: 6×OD; dynamic: 12×OD |
Impacted Resistant | Yes |
Weather Resistant | Yes |
Specific properties
-- Voltage range 600/1000 V
-- Routine voltage test, 5 min. 2 000 V IEC 811
-- Type voltage test, 15 min. in water 4 000 V IEC 811
-- Max. continuously current at ambient emp +30°C, per phase 324 A IEC 204-1
-- Max. temperature for 5 sec 250 °C
-- Max. short-circuit current for 5 seconds 4,2 kA
-- Permissible minimum bending radius 114 mm DIN 0298-3
-- Weight, total 2,7 Kg/m
CONSTRUCTION | NOMINAL DIAMETER OF SINGLE CORE | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT |
---|---|---|---|
NO. ×MM² | MM | MM | KG/KM |
7×25 | 9.6 | 35.0 | 2800 |
7×35 | 10.6 | 39.0 | 3500 |
7×50 | 11.8 | 42.9 | 4000 |
7×70 | 13.6 | 49.2 | 5440 |