10 mm2 PVC insulated single phase concentric Aluminum cable without two core copper communication cable
Guaranteed Technical Particulars
(10mm2 PVC Insulated Single Phase Concentric Aluminium Cable without Two core Copper Communication Cable)
Clause Number | KPLC Requirement | Bidder’s Offer | |||
Manufacturer’s Name and address |
Zhengzhou Yifang Cable Co.Ltd./ No.7, Changchun Road, High-Tech. Industry Area, Zhengzhou, China | ||||
Country of Manufacture | China | ||||
Bidder’s Name and address |
KENYA
|
||||
1. | Scope |
KP1/6C/13/TSP/05/033
|
|||
1.1-1.3 | |||||
2. | Applicable Standards | BS7870,BS6746, KS04-1022 | |||
3. | Terms&Definitions | For the purpose of this specification the definitions given in the reference standards shall apply | |||
4. | Requirements | ||||
4.1 | Service Conditions | The cable shall be a service cable for continuous operation outdoors and tropical conditions(temperature rang of -1℃ to +40℃, humidity of upto 90% and saline conditions along the coast),suitable for laying in cable ducts and in air,permissible continuous loading operating temperature shall be 70℃ and short circuit temperature of 160℃. | |||
4.2 | Materials&Construction | ||||
4.2.1 | General requirements | BS 7870-3.20:2001 and Kenya Standard KS 04-1022 | BS 7870-3.20:2001 and Kenya Standard KS 04-1022 | ||
4.2.2 | Phase conductor (Material & construction) | ||||
4.2.2.1 | Typical construction | Material | Circular stranded plain annealed aluminum Conductor Left Hand | ||
Direction of lay | |||||
4.2.2.2 | Insulation | As per KS 04-1022. KS 04-188 and BD 6746 | As per KS 04-1022. KS 04-188 and BD 6746 | ||
4.2.2.3 | Thickness of insulation | As per KS 04-1022 | Min.1.55mm | ||
4.2.3 | Concentric layer | ||||
4.2.3.1 | Neutral earth conductor (Material & construction) | ||||
4.2.3.1.1 | Typical construction | Material | Plain annealed aluminum wire | ||
Number of wires and the resistance of the earth-neutral conductors | 7, 3.08Ω/KM | ||||
4.2.3.1.2 | Direction of lay | Right Hand | |||
4.2.3.2 | Communication cable | ||||
4.2.3.2.1 | Construction | ||||
4.2.3.2.1.1 | |||||
4.2.3.2.1.2 | Material | As per BS 6360 and BS 2011, Test 2T, Method 1 | / | ||
4.2.3.2.1.3 | Length of lay | / | |||
Direction of lay of the strand | |||||
4.2.3.2.1.4 | Joints | Shall be essentially smooth, and shall not have any sharp projections | / | ||
4.2.3.2.1.5 | Colors | Correspond with standard colours shown in IEC 60304:1982 | / | ||
4.2.3.2.2 | Insulation | / | |||
Material | PVC compound-type TI1 as specified in KS 04-1022, KS 04-188 and BS 6746 | / | |||
Dimensions | As per table 2 | / | |||
4.2.4 | Over-sheath or Outer Jacket | ||||
4.2.4.1 | Material | As per KS 04-1022 and BS 6746 | As per KS 04-1022 and BS 6746 | ||
Oversheath testing | In accordance with KS 04-1022 | In accordance with KS 04-1022 | |||
4.2.4.2 | Minimum thickness | Shall not fall below the values on Table 2 by>(15%+0.1mm) | 0.31mm | ||
4.2.4.3 | Non-metallic rip-cord | Shall be laid under the sheath | Yes | ||
Shall incorporate the manufacturer’s identification colour | |||||
4.3 | Standard sizes and characteristics | As per table 2, Table 3 and as per the requirement of clause 4 of BS 7870-3.20:2001 | As reqired | ||
4.4 | Embossing on cable Oversheath (parameters to be indicated and method of marking) | ||||
4.5
|
Quality Management System | Yes | |||
Quality Assurance Plan | Yes | ||||
Copy of ISO 9001:2008 Certificate | Yes | ||||
Manufacturer’s experience | Yes | ||||
Manufacturing Capacity (units per month) | Yes | ||||
List of previous customers | Yes | ||||
Customer reference letters | Yes | ||||
5.1 | Test standards and responsibility of carrying out tests | KS 04-1022, BS 7870-3.20, BS 6746,BS4804-1,BS6360 | |||
5.2 | Copies of Type Test Reports submitted with tender | Yes | |||
5.3 | Acceptance testes to be witnessed by KPLC at factory before shipment | Yes | |||
5.4 | Test reports to be submitted by supplier to KPLC for approval before shipment | Yes | |||
5.5 | Replacement of rejected cables | Yes | |||
6.1 | Markings | As required | |||
6.2 | Packing | Wooden Drum | |||
7.1 | Documents submitted with tender | Yes | |||
7.2 | Documents to be submitted by supplier to KPLC for approval before manufacture | Yes | |||
8.0 | Statement of compliance to specification | Yes |