Specifications
Brand Name :
GFUVE
Model Number :
GF1061B
Certification :
CE, ISO9001
Place of Origin :
BEIJING CHINA
MOQ :
1SET
Price :
Negotiable
Payment Terms :
L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :
200SETS/MONTH
Delivery Time :
2-3weeks
Packaging Details :
Standard Export Wooden Box
Name :
GFUVE CT analyzer
Application :
ct and pt test
Theory :
DC variable-frequency methods
LCD :
7inch TFT touch color LCD
Accuracy :
0.02% or 0.05%
Reference standards :
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Ratio error :
0.02%
Weight :
4KG
Overall dimension (L x W x H) (mm) :
280 x 250 x 160mm
Usage :
Measurement CT and Protection CT
Description

Portable GFUVE CT Analyzer with PT testing function, current transformer testing

GF1061B Portable GFUVE CT Analyzer with PT testing function, current transformer testing

GF1061 portable GFUVE CT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1

Injects low test signals into secondary side of the CT

Determines the CT‘s equivalent circuit parameters

Identifies all relevant CT performance parameters

Displays all relevant parameters of the CT and its accuracy at different currents and burdens

Evaluates the CT according to the selected standard

Determines unknown CT nameplate parameters

Demagnetizes the CT after the test

Ratio and phase accuracy
Winding resistance
Excitation characteristics (knee points)
Composite error (ALF, ALFi, FS, FSi, Vb)
Burden impedance
Transient CT classes and parameters
(TPS, TPX, TPY and TPZ type CTs)
Transient dimensioning factor (Ktd)
If missing/unknown: CT type, class, ratio, knee point, power factor, nominal burden, operating burden, primary and secondary winding resistance
Remanence and residual magnetism
Immediate good/bad evaluation

Features

1. Steady and transient state characteristic tests of various types of CT/PT

2. The use of advanced power technology, the test knee point reaches up to 50kV

3. No external other auxiliary equipment, stand-alone to complete all test items

4. CT test, easy to test, all the tests are using the same wire connection except the load test

5. It carries with thermal printer, so it can print test results on site Reference Standard IEC 60044, ANSI/ IEEE C57.13, IEC61869, GB 1207-2006, GB 1208-2006

6. Parameters such as knee point current and voltage

7. Parameters such as 10% error curve, 5% error curve

8. With battery, working 7days.

9. The device can store 10000 groups of test data which would not be lost if the device is power off.

10. The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word file report

11. Portability: weight <4kg, the best light ct analyzer

MAIN FUNCTIONS

I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity
4. 5% and 10% error curve 4. Ratio error, phase error
5. Accuracy limiting factor (ALF) 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Ratio error, phase error 7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test 
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

PARAMETERS

Electrical parameters
Accuracy 0.05%
Power supply AC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage 0-100Vrms
Output current 0-5Arms (20A peak-value)
Output power 0-400 VA (1500 VApeak)
Automatic frequency variation range 0.1-60Hz
Equivalent excitation voltage ≤5000V
Accuracy ≤0.5%
Secondary winding DC resistance measurement Range 0.1-1000Ω
Accuracy ≤0.05%
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5%±0.1VA
CT/PT phase error measurement Accuracy ±1min (typical) / 3 min (guaranteed)
Resolution 0.1min
CT ratio error measurement Range 1-50000
Accuracy ≤0.05%
PT ratio error measurement Range 1-10000
Accuracy ≤0.05%
Standards 
Reference standards GB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm) 280 x 250 x 160
Weight (kg) ≤4
Environmental conditions 
Relative humidity Relative humidity 5%-95% not condensing
Operating temperature -10°C to +50°C
Storage temperature -20°C to +70°C
Altitude ≤1000m

Photo

Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1

Send your message to this supplier
Send Now

Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1

Ask Latest Price
Watch Video
Brand Name :
GFUVE
Model Number :
GF1061B
Certification :
CE, ISO9001
Place of Origin :
BEIJING CHINA
MOQ :
1SET
Price :
Negotiable
Contact Supplier
video
Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1
Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1
Portable GFUVE CT PT Analyzer Current Transformer Testing IEC60044-1

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Active Member
8 Years
beijing, beijing
Since 2008
Business Type :
Manufacturer
Total Annual :
$100,000,000-$150,000,000
Employee Number :
300~350
Certification Level :
Active Member
Contact Supplier
Submit Requirement