TEST-901 PORTABLE 1000A SMART PRIMARY CURRENT INJECTION TESTER WITH 5KVA CAPICITY
PORTABLE 1000A SMART PRIMARY CURRENT INJECTION TESTER WITH 5KVA CAPICITY
TEST-901 1000A PRIMARY CURRENT INJECTION TESTER of circuit breaker adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 primary current injection test system is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
This powerful test system is designed for primary injection testing of protective relay equipment and circuit breakers. It is also used to test the turns ratio of current transformers and for other applications that require high variable currents.
Primary current injection testing system is utilised in high current/high voltage scenarios found at large electrical installations such as substations. A large current (between 100A and 20,000A depending on system specifications and test requirements) is injected directly on the primary side of the electrical system such as a circuit breaker. The objective of the test is to identify how the system operates under various levels of current load.
Primary injection testing system is suitable for testing over-current trip relays attached to a circuit breaker. By injecting the current into the system we can measure if the breaker will trip or fail, and how long the current is live before the circuit is broken.
Circuit breakers can go long periods of time without activation, and failure at the moment of activation can cause catastrophic damage to the electrical system. Circuit breaker testing with primary current injection on a breaker that has not triggered in some time is the best way to recreate the real operating conditions of a current spike.
FEATURES
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply(AC) | 220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz |
Current Output (AC) | 1000A·5V or 500A·10V |
Capacity | 5KVA |
The current output waveform distortion | ≤5% |
Dual protection | overload electronic protection and software protection |
Primary current | |
Range | 0-1100A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
1000A range | 1000A 2-3minutes 500A 3-6minutes |
500A range | 500A 2-3minutes |
With timer | |
Range | 0.0001~999.99S |
Resolution | 0.001S |
Accuracy | <0.5%±5 words |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 430×260×260 |
Weight(kg) | 25 |
Environmental conditions | |
Temperature | -10°C to 40°C |
Relative humidity | ≤80% |
Model | ACCU RACY | Primary current | AMMETER (0-6A) | TIMER | POWER | INJECTION CURRENT TIME | DIMENSION(W×D×H)(mm) | WEIGHT | REMARK |
---|---|---|---|---|---|---|---|---|---|
TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min | 430×260×260 | 25KG | Integrated structure |
TEST-902 | 0.5% | 0-2200A | YES | OPTIONAL | 12KVA | 2000A:2-3min; 1000A:3-6min | 360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
TEST-903 | 0.5% | 0-3300A | YES | OPTIONAL | 15KVA | 3000A:2-3min; 1500A:3-6min | 380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
TEST-905 | 0.5% | 0-5500A | YES | OPTIONAL | 25KVA | 5000A:2-3min; 2500A:3-6min | 430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |