T-212 Portable Circuit Breaker 100A Contact Resistance Test Equipment
T-212 contact resistance MicroOhm Meter tester adopts the top open structure or vehicle mounted horizontal chassis. It has that vantage: more small volume, more light weight, more strong functions, and the simple operation. It designed for field tester design. The high output voltage is10V. Display is160*128 large LCD screen. Test current optionally, test time can be set, test process dynamic tips, suitable for different working environment. It can save 200 test record, the records can be printed and uploaded to the computer.
We ensure that our Contact Resistance tests sets are portable, making them suitable for field measurements. Our contact resistance testers’ portability makes them ideal for a vast range of resistance testing across the entire LV, MV HV and EHV spectrum. T-212 100A Circuit Breaker Contact Resistance Test Equipment According to the requirements of the new power Preventive testing procedures, conductive loop resistance testing of various switching devices is must be measured, whose testing current can not be less than 100A, Continuous Current time shall not be less than one minute.
We are offering Contact Resistance Micro Ohm Meter to our clients. Features: Technically advanced; Uses Kelvin four wire measurement principle; Long lasting; Current (DC): 100 A; Resistance Range: 199.9 μΩ & 1999 μΩ; Best Resolution: 0.1 µΩ & 1 μΩ; Accuracy: Value ± 0.5 % ± 1 Digit; Display: Two Nos, 4½ Digit, ½ Inch LCD for Resistance & Current Display.
200A High Current Contact Resistance Meter
Technical Data
Product Model | T-212 |
Rated working condition | Operating temperature: - 10℃ to 50℃; storage: - 20℃ to + 70℃. Relative humidity : 5 - 85%, without condensing. |
Power supply | AC 220V/240V±10% AC, 50Hz/60Hz + 10% |
Cooling way | intermittent air cooled |
Current output | constant current:100Amp, 200Amp. |
Test time | 100Amp:5-60Sec, 200Amp:5-30Sec |
Test indicator | |
Test range | 0-20000.0μΩ(100Amp) 0-10000.0μΩ(200Amp) |
Accuracy | 0.5%±2bit;resolution:0.1μΩ |
Max storage volume | 200 |
LCD | 5.7″black and white LCD display |
Communication | RS232 and USB communication interface |
Printer | internal installed 58mm wide thermal printer. |
Standard | DL/T 596 — 2005 |
DIMENSIONS | 415mm×319mm×168mm |
WEIGHT | 7.5kg |
Type | Contact resistance (μΩ) | Type | Contact resistance (μΩ) |
SN1-10 | <95 | DW1-60G | 200 |
SN2-10G | 75 | SW1-110 | 700 |
SN4-10 | 50—60 | SW2-110I | 180 |
SN4-20 | 50—60 | SW3-110 | 160 |
SN4-10G | 20 | SW4-110 | 300 |
SN4-20G | 20 | SW6-110 | 180—220 |
SN5-10 | 100 | SW2-220 | 400 |
SN6-10 | 80 | SW4-220 | 600 |
SN10-35 | <75 | SW6-220 | <400 |
DW1-35 | 550 | SW7-220 | <190 |
DW1-60 | 500 | KW1-220 | 400 |
DW3-110 | 1100—1300 | KW2-220 | 170 |
DW2-110 | 800 | KW3-220 | 110 |
KW1-110 | 150 | KW4-220 | 130 |
KW3-110 | 45 | DW2-220 | 1520 |
KV4-110A | 60 | DW3-220 | 1200 |
DW3-110G | 1600—1800 | SW6-330 | ≯600 |