ZONCN T9000 Series Advanced Vector Control Inverter
ZONCN is one of a leading manufacturer which specialized in inverter in China, our headquaters is located in Shanghai. ZONCN focus on the research and development, production, sales and the service of inverters. ZONCN has 6 mains general series of inverters and they are used widely in various applications. The voltage ranges from 110v to 1140v, power range covers 0.4kw to 1000kw. ZONCN has more than 80 dealers in China and abroad. Now our products are exported to more than 50 countries in Asia, Europe, Africa and America. ZONCN will always dedicate in the field of inverters, and warmly welcome you to be our partner.
Model | Input Voltage (V) | Rated output power(kW) | Rated input current(A) | Rated output current(A) | Motor Power (KW) |
T9200-0R4G | 1PH AC 220V±15% | 0.4 | 5.4 | 2.5 | 0.4 |
T9200-0R75G | 0.75 | 7.2 | 5 | 0.75 | |
T9200-1R5G | 1.5 | 10 | 7 | 1.5 | |
T9200-2R2G | 2.2 | 16 | 11 | 2.2 | |
T9200-3R7G | 3.7 | 17 | 16.5 | 3.7 | |
T9200-5R5G | 5.5 | 26 | 25 | 5.5 | |
T9200-7R5G | 7.5 | 35 | 32 | 7.5 | |
T9400-0R4G | 3PH AC 380V±15% | 0.4 | 3.4 | 1.2 | 0.4 |
T9400-0R75G | 0.75 | 3.8 | 2.5 | 0.75 | |
T9400-1R5G | 1.5 | 5 | 3.7 | 1.5 | |
T9400-2R2G | 2.2 | 5.8 | 5 | 2.2 | |
T9400-3R7G/5R5P | 3.7/5.5 | 10/15 | 9/13 | 3.7/5.5 | |
T9400-5R5G/7R5P | 5.5/7.5 | 15/20 | 13/17 | 5.5/7.5 | |
T9400-7R5G/11P | 7.5/11 | 20/26 | 17/25 | 7.5/11 | |
T9400-11G/15P | 11/15 | 26/35 | 25/32 | 11/15 | |
T9400-15G/18.5P | 15/18.5 | 35/38 | 32/37 | 15/18.5 | |
T9400-18.5G/22P | 18.5/22 | 38/46 | 37/45 | 18.5/22 | |
T9400-22G/30P | 22/30 | 46/62 | 45/60 | 22/30 | |
T9400-30G/37P | 30/37 | 62/76 | 60/75 | 30/37 | |
T9400-37G/45P | 37/45 | 76/90 | 75/90 | 37/45 | |
T9400-45G/55P | 45/55 | 92/113 | 90/110 | 45/55 | |
T9400-55G | 55 | 113 | 110 | 55 | |
T9400-75G/90P | 75/90 | 157/180 | 150/176 | 75/90 | |
T9400-90G/110P | 90/110 | 180/214 | 176/210 | 90/110 | |
T9400-110G/132P | 110/132 | 214/256 | 210/253 | 110/132 | |
★Due to space limitation, please contact us for powers above 110kw |
Item | Description | |||
Basic function | Control Mode | VF control | ||
Sensorless flux vector control(SVC) | ||||
Close-loop vector control(FVC)(Above 3.7kW) | ||||
Maximum frequency | 0~600Hz | |||
Carrier frequency | 0.5kHZ——8kHz | |||
The carrier frequency is automatically adjusted based on the load features | ||||
Input frequency resolution | Digital setting:0.01Hz | |||
Analog setting: Maximum frequency x 0.025% | ||||
Start torque | G Type:0.5Hz/150%(SVC) | |||
P Type:0.5Hz/100% | ||||
Speed range | 1:100 (SVC) | |||
Speed stability accuracy | ±0.5%(SVC) | |||
Overload capacity | G Type:60s for 150% of the rated current, 3s for 180% of the rated current. P Type:60s for 120% of the rated current, 3s for 150% of the rated current. | |||
Torque boost | Auto-boost ; | |||
Customized boost: 0.1%~30.0% | ||||
V/F Curve | Straight-line V/F curve | |||
Multi-point V/F curve | ||||
N-power V/F curve (1.2-power, 1.4-power, 1.6-power, 1.8-power, square) | ||||
V/F separation | 2 types: complete separation; half separation | |||
Ramp Mode | Straight-line ramp. | |||
Four groups of acceleration/deceleration time with the range of 0.00`6500.0s | ||||
DC braking | DC braking frequency:0.00Hz~Maximum frequency | |||
Braking time:0.0s~36.0s | ||||
Braking action current value:0.0%~100.0% | ||||
JOG control | JOG frequency range:0.00Hz~50.00Hz | |||
JOG acceleration/deceleration time: 0.0s~6500.0s. | ||||
Simple PLC,Multiple preset speeds | It implements up to 16 speeds via the simple PLC function or combination of terminal states | |||
Onboard PID | It realizes process-controlled closed loop control system easily | |||
Auto voltage regulation(AVR) | It can keep constant output voltage automatically when the mains voltage | |||
Overvoltage/overcurrent stall control | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to over voltage/over current | |||
Rapid current limit | It helps to avoid frequent over current faults of the AC drive. | |||
Torque limit and control | It can limit the torque automatically and prevent frequent over current tripping during the running process. Torque control can be | |||
implemented in the FVC mode. | ||||
Support for multiple PG card | Support for differential input PG card, resolver PG card ,rotating transformer PG card |