In industrial applications, safety always comes first. The Z5000-BF series drives understand this and are equipped with multiple safety protection features including timing, antifreeze and waterless alarms. The timing function allows users to set the running time of the device according to actual requirements to avoid potential security risks caused by unattended operation for a long time. The antifreeze function can automatically start the heating device in a low temperature environment to prevent the pipeline from freezing; The no water alarm function can immediately issue an alarm when the system is short of water to avoid idling damage to the equipment. These meticulous safety designs build a solid line of defense, so that users can enjoy efficient production at the same time, but also have a full sense of security.
Power quality is one of the key factors that affect the stability and life of equipment. Z5000-BF series inverter built-in efficient EMC (electromagnetic compatibility) filter, like an invisible barrier, effectively filter out impurities and harmonics in the current, to ensure the purity and stability of the output power. According to the experimental data, after the use of this series of frequency converter, the harmonic content of the power grid can be reduced to below the national standard, reducing the electromagnetic interference on other equipment, but also protect the frequency converter itself from the influence of power grid fluctuations, and extend the service life of the equipment.
Item | Z5000-BF Series | |
Basic function | Control Mode | Sensorless flux vector control(SFVC) Voltage/Frequency (V/F) Control |
Maximum frequency | Vector control:0-320Hz V/F control:0-3200Hz | |
Carrier frequency | 1kHz~16kHz The carrier frequency is automatically adjusted based on the load features. | |
Input frequency resolution | Digital setting:0.01Hz Analog setting: Maximum frequency 0.025% | |
Start torque | P: Type:0.5Hz/100% | |
Speed range | 1:100(SVC) | |
Speed stability accuracy | ±0.5%(SVC) | |
Overload capacity | G Type:60s for 150% of the rated current, 3s for 180% of the rated current. P Type:60s for 120% of the rated current, 3s for 150% of the rated current. | |
Torque boost | Auto-boost ; Customized boost:0.1%~30.0% | |
VF curve | Line V/F curve;Multi-point V/F curve;N-power V/F curve | |
VF separation | 2 types: complete separation;half separation | |
Ramp Mode | Straight-line ramp;S-curve ramp;Four groups of acceleration/deceleration time:0~6500.0s | |
Auto voltage regulation(AVR) | It can keep constant output voltage automatically when the mains voltage changes | |
Rapid current limit | It helps to avoid frequent over current faults of the AC drive. | |
Torque limit and control | It can keep constant output voltage automatically when the mains voltage changes | |
Onboard PID | It realizes process-controlled closed loop control system easily | |
JOG control | JOG frequency range: 0.00–50.00 Hz JOG acceleration/deceleration time: 0.0–6500.0s | |
DC braking | DC braking frequency:0.00Hz to maximum frequency Braking time:0.0-100.0s Braking action current value:0.0%-100.0% | |
Instantaneous blackout doesn’t stop | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time. | |
Timing control | Timing range:0.0Min~6500.0Min | |
Communication | RS485 | |
Run command channel | Given by the panel,control terminals,serial communication port,can be switched by many ways | |
Frequency source | 10 kinds of frequency source, given by digital analog voltage, analog current, pulse, serial port. It can be switched by many ways | |
Other functions | Auxiliary frequency source | 10 kinds of frequency source, can easily realize micro adjustment, frequency Synthesizer |
Input terminals | 6 digital input terminals, one of which supports up to100 kHz high-speed pulse input (optional). 2 analog input terminal, one of which only supports0-10 V voltage input and the other supports 0-10V voltage input or 4-20 mA current input. | |
Output terminals | 1 digital output terminal 1 relay output terminal 1 analog output terminal: that supports 0-20 mA current output or 0-10v voltage output | |
Multiple protection modes | Motor short-circuit detection at power-on, output phase loss protection, over-current protection, over-voltage protection, under voltage protection, overheat protection and overload protection. |
Model | Rated output power (kW) | Rated input current (A) | Rated output current (A) | Motor Power (kW) |
Input voltage(v):1PH AC 220V±15% | ||||
Z5200A0D75K-BF | 0.75 | 7.2 | 5 | 0.75 |
Z5200A01D5K-BF | 1.5 | 10 | 7 | 1.5 |
Z5200A02D2K-BF | 2.2 | 16 | 11 | 2.2 |
Input voltage(v):3PH AC 380V±15% | ||||
Z5400A0D75K-BF | 0.75 | 3.8 | 2.5 | 0.75 |
Z5400A01D5K-BF | 1.5 | 5 | 3.7 | 1.5 |
Z5400A02D2K-BF | 2.2 | 5.8 | 5 | 2.2 |
Z5400A03D7K-BF | 3.7 | 10 | 9 | 3.7 |
Z5400A05D5K-BF | 5.5 | 15 | 13 | 5.5 |
Z5400A07D5K-BF | 7.5 | 20 | 17 | 7.5 |
Z5400A0011K-BF | 11 | 26 | 25 | 11 |
Z5400A0015K-BF | 15 | 35 | 32 | 15 |
Z5400A0018K-BF | 18 | 38 | 37 | 18 |
Z5400A0022K-BF | 22 | 46 | 45 | 22 |
Z5400A0030K-BF | 30 | 62 | 60 | 30 |
Z5400A0037K-BF | 37 | 76 | 75 | 37 |
Z5400A0045K-BF | 45 | 92 | 90 | 45 |
Z5400A0055K-BF | 55 | 113 | 110 | 55 |
Z5400A0075K-F | 75 | 157 | 150 | 75 |
Z5400A0090K-BF | 90 | 180 | 176 | 90 |
Z5400A0110K-BF | 110 | 214 | 210 | 110 |
Z5400A0132K-BF | 132 | 256 | 253 | 132 |
Z5400A0160K-BF | 160 | 307 | 300 | 160 |
Model | Motor | Output Current | Mounting dimension(mm) | |||||
Overall dimension | ||||||||
W | H | D | A | B | Φd | |||
Z5200A0D75K-BF | 0.75 | 5 |
188 |
122 |
134 |
178 |
105 |
4 |
Z5200A01D5K-BF | 1.5 | 7 | ||||||
Z5200A02D2K-BF | 2.2 | 11 | ||||||
Z5400A0D75K-BF | 0.75 | 2.5 | ||||||
Z5400A01D5K-BF | 1.5 | 3.7 | ||||||
Z5400A02D2K-BF | 2.2 | 5 | ||||||
Z5400A03D7K-BF | 3.7 | 9 |
235 |
154 |
179 |
225 |
129 |
4 |
Z5400A05D5K-BF | 5.5 | 13 | ||||||
Z5400A07D5K-BF | 7.5 | 17 | ||||||
Z5400A0011K-BF | 11 | 25 | ||||||
Z5400A0D75K-BF-V | 0.75 | 2.5 |
140 |
190 |
138 |
130 |
160 |
4.5 |
Z5400A01D5K-BF-V | 1.5 | 3.7 | ||||||
Z5400A02D2K-BF-V | 2.2 | 5 | ||||||
Z5400A03D7K-BF-V | 3.7 | 9 |
192 |
280 |
178 |
180 |
200 |
5.5 |
Z5400A05D5K-BF-V | 5.5 | 13 | ||||||
Z5400A07D5K-BF-V | 7.5 | 17 | ||||||
Z5400A0011K-BF-V | 11 | 25 | ||||||
Z5400A0015K-BF | 15 | 32 | ||||||
Z5400A0018K-BF | 18 | 37 | 236 | 300 | 204 | 225 | 250 | 7 |
Z5400A0022K-BF | 22 | 45 | ||||||
Z5400A0030K-BF | 30 | 60 | 236 | 400 | 231 | 225 | 175+175 | 7 |
Z5400A0037K-BF | 37 | 75 |
Note:
380v/0.75-11kw Horizontal installation and vertical installation exist at the same time. -V indicates vertical installation. Above 15kw is installed vertically.
1:What is your MOQ?
1 PC.
2:What is terms of payment?
T/T 100% before delivery.
3:What is your delivery time?
Fast delivery is our advantage. Usually within ten days.
4:How can we do OEM/ODM?
We do OEM for more than 40 brands. If your order reaches a certain quantity, we can do it for you.